9
To connect the IDNet card to devices using Class A wiring, read the following instructions and
refer to Figure 5, below.
1.
Route wire between 12 and 18 AWG from the , IDNetB-, and SHIELD outputs
on TB1 of the IDNet card to the appropriate inputs on a peripheral IDNet appliance.
Note:
Use ferrite beads as shown.
2.
Route wire from the first IDNet appliance to the next one. Repeat for each appliance.
3.
Route wire from the last IDNet appliance to the and IDNetA- inputs on TB1 of
the IDNet card.
+
1
2
1
2
1
2
Figure 5. Class A Wiring
Continued on next page
Step 3. Wiring to IDNet Peripherals,
Continued
Class A Wiring
IDNET CARD
IDNET DEVICES
12 to 18 AWG
SHIELD
SHIELD
FERRITE BEAD
(required)
FERRITE BEAD
(required)