User manual for - FLOW METER SPI-N118
Register Write
Range
Register description
40h
41h
Yes
Yes
0 ÷ 999999 “
SEt P
” parameter in “
rELAy2
” menu, no decimal point included
42h
43h
Yes
Yes
0 ÷ 99999
“
HySt
” parameter in “
rELAy2
” menu, no decimal point included
44h
Tak
0 ÷ 5
“
modE
” parameter in “
rELAy2
” menu:
0
- “
noACt
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modbuS
” mode
45h
Yes
0 ÷ 999
“t on”
parameter in
“rELAy2”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
46h
Yes
0 ÷ 999
“t oFF”
parameter in
“rELAy2”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
47h
Yes
0 ÷ 1
“unit”
parameter in
“rELAy2”
menu:
0
- seconds;
1
- minutes
48h
Yes
0 ÷ 2
“ALArmS”
parameter in
“rELAy2”
menu:
0
- no changes;
1
- on;
2
- off
49h
4Ah
Yes
Yes
0 ÷ 999999 “
SEt P2
” parameter in “
rELAy2
” menu, no decimal point included
4Bh
Yes
0 ÷ 2
“SourCE”
parameter in
“rELAy2”
menu (kind of value controlled
relay):
0
- “FLo”;
1
- “bAt”;
2
- “tot”;
4Ch
Yes
0 ÷ 3
“t PrEc”
parameter in
“rELAy2”
menu (precision of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- “ 0”;
1
- “ 0.0”;
2
- “ 0.00”;
3
- “0.000”
4Dh
Yes
0 ÷ 1
“t unit”
parameter in
“rELAy2”
menu (the unit of thresholds and
hysteresis while relay is controlled due to total flow counter value):
0
- lit.;
1
- m
3
;
70h
Yes
0 ÷ 1
“
modE
” parameter in “
HOLd
” menu (type of detected changes):
0
- peaks;
1
- drops
71h
72h
Yes
0 ÷ 999999 “
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included)
73h
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks' (or drops')
display time expressed in seconds
74h
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu (the type of values displayed on
the display
):
0
- current measurement value;
1
- peaks (or drops) values
75h
Yes
0 ÷ 1
“
H r1
” parameter in “
HOLd
” menu (the control mode of relay R1 and
LED R1)
:
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
76h
Yes
0 ÷ 1
“
H r2
” parameter in “
HOLd
” menu (the control mode of relay R2 and
LED R2) :
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
40