2899
10
GB
6.
FAULTS / SOLUTIONS
Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner.
A fault usually makes the lock-out lamp light which is situated inside the reset button of the control box
(1, fig. 1, page 1).
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found.
WARNING
The manufacturer cannot accept responsibility for any damage to persons, animals or property due to error in
installation or in the burner adjustment, or due to improper or unreasonable use or non observance of the
technical instruction enclosed with the burner, or due to the intervention of unqualified personnel.
FAULTS
POSSIBLE CAUSES
SOLUTION
All led are off and
the burner does not
start.
Lack of electrical supply.
Check presence of voltage in the
L1 - N clamps of the 7 pin plug.
Check the conditions of the fuses.
Check that safety thermostat is not
lock out.
The connections in the control box are
wrongly inserted.
Check and connect completely all the
plugs.
The orange led is
always on and the
b u r n e r d o e s n o t
start.
Heater and start thermostat are faulty.
Replace them.
The green led is on
and the burner re-
mains in the pre-
purge phase.
The flame detector sees false light.
Eliminate the light.
B u r n e r r u n s n o r-
m a l l y i n t h e p r e -
purge and ignition
cycle and locks out
after 5 seconds ca.
The flame detector is dirty.
Clear it.
The flame detector is defective.
Change it.
Flame moves away or fails.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
Check the coil of solenoid valve.
Burner starts with
an ignition delay.
The ignition electrodes are wrongly
positioned.
Adjust them according to the
instructions of this manual.
Air output is too high.
Set the air output according to the
instructions of this manual.
Nozzle dirty or worn.
Replace it.