2.2
CHARACTERISTICS
OF FEEDWATER
IT IS ABSOLUTELY ESSENTIAL THAT
THE WATER USED FOR THE CENTRAL
HEATING SYSTEM SHOULD BE TREA-
TED IN THE FOLLOWING CASES:
–very extensive systems (with high
contents of feedwater);
–frequent addition of makeup water
into the system;
–should it be necessary to empty the
system either partially or totally.
2.3
SYSTEM FILLING
Before proceeding to connecting up
the boiler, you are recommended to
get air to circulate in the piping in
order to eliminate any foreign bodies
that might be detrimental to the ope-
rating efficiency of the appliance.
Filling must be done slowly so as to
allow any air bubbles to be bled off
through the air vents provided on the
heating system.
The pressure of cold charging of the
system, and the pressure of pre-pres-
surization of the expansion vessel,
must correspond, or in any case must
not be less than, the height of the sta-
tic column of the system (e.g., for a sta-
tic column of 5 m, the pre-pressuriza-
tion pressure of the expansion vessel
and the charging pressure must cor-
respond to at least 0.5 bar).
2.4
CONNECTING UP FLUE
The flue for evacuation into the atmo-
sphere of the products of combustion
from natural draught appliances must
meet all national and local regulations in
force and the following requirements:
–be gas-tight to the products of com-
bustion, waterproof and thermally
insulated;
–be built of materials suitable for
resisting over time normal mechani-
cal stresses, heat, and the action of
products of combustion and their
possible condensates;
–follow a vertical path and not pre-
sent any throttling throughout its
entire length;
–be adequately insulated to prevent
phenomena of condensation or coo-
ling of fumes, in particular if located
outside the building or in unheated
ambiences;
–be set at an adequate distance
from combustible or easily inflam-
mable material by means of an air
gap or suitable insulating material;
–have beneath the mouth of the first
smoke duct a chamber for collecting
solid material and any condensate;
the height of the chamber must be
at least 500 mm. Access to the
chamber must be guaranteed by
means of an opening provided with
an air-tight metal door;
–have a circular, square, or rectangu-
lar internal cross section; in the
case of square or rectangular sec-
tions, the corners must be rounded
off with a radius of not less than 20
mm. However, hydraulically equiva-
lent cross sections are allowed;
–be equipped with a chimney-pot at
the top, which must be outside the
so-called back-flow zone, so as to
prevent the formation of back-flow,
which prevents free discharge of
the products of combustion into the
atmosphere;
–be devoid of mechanical means of
suction located at the top of the pipe;
–no overpressure should be present
in a chimney that passes within or
close up to inhabited rooms.
2.4.1
Sizing of flue
The correct sizing of the flue is an
essential condition for efficient boiler
operation.
To determine the useful section of the
flue, it is necessary to refer to all natio-
nal and local regulations in force.
The main factors to be taken into con-
sideration for calculating the section
are the heat input of the boiler, the
type of fuel, the percentage of CO
2
,
the mass flow of smoke at nominal
load, the temperature of the smoke,
the roughness of the internal wall, and
the effect of gravity on the draught
pressure, which must take into
account the external temperature
and the altitude.
Table 1 gives the specific parameters
for the boilers of the
“RS”
series.
2.5
BOILER BODY
The boiler body comes supplied assem-
bled. Where there is difficulty in gaining
access to the boiler room, the body
can be supplied in separate sections.
For assembly, proceed as follows:
– prepare the sections, cleaning the seats
of the tapered nipples with solvent;
–insert the bead of putty (fig. 2) in the
groove provided for fume tightness,
pressing lightly;
–prepare one of the two intermediate
sections having bosses with 1/2”
holes. After lubricating them with
boiled linseed oil, insert the tapered
nipples (fig. 3);
51
TABLE 1
Heat input
Smokes temperature
Smoke flow
kW
°C
gr/s
RS 6
121.7
136
104.2
RS 7
145.9
154
109.4
RS 8
170.0
170
111.7
RS 9
194.2
173
118.6
RS 10
218.2
153
160.8
RS 11
242.1
160
164.2
RS 12
266.0
143
206.9
RS 13
290.0
148
213.6
RS 14
313.6
154
212.5
Fig. 2
Fig. 3
Summary of Contents for RS 10
Page 1: ...RS IT ES GB PT...