6
1.3
TECHNICAL FEATURES
MURELLE GREEN PLANET 110 HE I/E
Heat output
Nominal (80-60°C)
kW
105,6
Nominal (50-30°C)
kW
114.6
Reduced (80-60°C)
kW 21.1
Reduced
(50-30°C) kW
23.6
Heat input nominal*
kW
108,0
Heat input reduced*
kW 21,6
Max/min useful yield (80-60°C)*
% 97.7/97.8
Max/min useful yield (50-30°C)*
% 109.1/106.1
Termal efficiency (CEE 92/42 directive)
★★★★
Losses after shutdown to 50°C (EN 483)
W 126
Supply voltage
V-Hz 230-50
Adsorbed power consumption
W 309
Electrical protection grade
IP X4D
C.H. setting range
°C 20/80
Water content boiler
l 8.2
Maximum water head
bar 5
Maximum temperature
°C 85
Capacity of the heating expansion vessel
l --
Pressure of the heating expansion vessel
bar --
D.H.W. setting range
°C --
D.H.W. flow rate (EN 625)
l/min --
Continuous D.H.W. flow rate ∆t 30°C
l/min --
Minimum D.H.W. flow rate
l/min --
D.H.W. pressure min/max
bar --
D.H.W. pressure min. nom. power
bar --
Exhaust fumes temperature at max flow rate (80-60°C)
°C 86.2
Exhaust fumes temperature at min. flow rate (80-60°C)
°C 74.6
Exhaust fumes temperature at max flow rate (50-30°C)
°C 61.6
Exhaust fumes temperature at min. flow rate (50-30°C)
°C 49.2
Smokes flow min/max
kg/h 37/186
CO
2
at max/min flow rate G20
% 9.0/9.0
CO
2
at max/min flow rate G31
% 10.2/10.2
CE certification
n° 1312CM5614
Category
II2H3P
Type
B23-53/B23P-53P/C13-33-43-53-83
NOx emission class
5 (
<
30 mg/kWh)
Weight when empty
kg 87
Main burner nozzle
Quantity nozzles
n° 1
G20 nozzle diameter
ø
12.4
G31 nozzle diameter
ø
8.2
Consumption at maximum/minimum flow rate
Maximum G20
m
3
/h 11.42
Minimum G20
m
3
/h 2.28
Maximum G31
kg/h
8.38
Minimum G31
kg/h 1.68
Gas supply pressure
G20
mbar 20
G31
mbar 37
* They are obtained by low heating value = 34,02 MJ/m3