17
ATTENTION:
- Before fitting the accessories, it is always advisable to lubricate the internal section of the gaskets with silicon products, avoid
the use of oils and greases.
Fig. 7
C Type (ø 80 separate pipes)
WARNING !
When load loss of the individual accessories connec-
ted exceeds i 4 mm H2O, to assure correct opera-
tion of the appliance, do as follows:
- set the installer parameter PAR 9 as indicated in
TABLE 2 (see point 3.3 to access the installer para-
meters).
- proceed with calibrating CO2 at the maximum and
minimum capacity as specified in point 4.2.2.
TABLE 2
Load loss
PAR 9
(mm H2O)
(long chimneys)
0 - 4
0
4 - 8
1
8 - 12
2
12 - 16
3
16 - 20
4
20 - 24
5
24 - 28
6
28 - 32
7
32 - 36
8
36 - 40
9
40 - 42
10
80 mm accessories
Key Code
Description
Load loss mm H20
Inlet
Exaust
1
8077450 90° bend - 80 mm
2,3
3,5
2a
8077351 1000mm Extension - 80mm
1,4
1,4
2b
8077350 500mm Extension - 80mm
0,7
0,7
3
8091300 Articulated Tile
-
-
4
8091204 Roof terminal(L 1381mm)
-
5,0
5
6296513 Extension with test point(L 250mm)
-
0,3
6
8077451 45° bend - 80mm
1,7
2,3
7
8089501 Exhaust terminal - 80mm
-
4,0
8
8091500 Inner/outer wall seal (2 of each)
-
-
9
8089500 Inlet terminalm - 80mm
1,8
-
11
Gasket (supplied with boiler)
-
-
600