MODBUS mode (fig. 4/d)

This mode allows for MODBUS commu-
nication of at least two boilers in cascade 
and is performed by requesting another 
RS-485  board  provided  in  the  kit  code 
8092244. 

ATTENTION:  Communication  will  occur 
only  with  the  MASTER  boiler,  (boiler 
with PAR 15 = 0), interpreting the casca-
de as a single heat capacity generator: 

CASCADE

 = P 

BOILER

 x No. 

BOILERS

.

To  install  the  second  board,  proceed  as 
follows:

-  Remove  the  cover  and  electrical-

ly  connect  the  second  RS-485  board 
equipped with lid to the RS-485 board 
already installed in the MASTER boiler 
(boiler with 

PAR 15 = 0

) with the wired 

connector provided in the kit.

 

CAUTION: Insert  the wired connector 
with caution.

-  Set the DIP SWITCH of the new board 

in MODBUS mode.

-  Close the lid of the second board.
-  Choose  the  communication  configu-

ration suited to the MODBUS network 
(PAR 17 INST) according to 

Table PAR 

17 INST

.

RS-485 connection to the INSOL/MIXED 
ZONE (fig. 4/e)

The  RS-485  board  can  be  connected 
to  optional  INSOL  kit  code  8092254  or 
MIXED ZONE code 8092252. Both require 
the board housing kit code 8092236.
Carry  out  the  electrical  connections  as 
indicated in the figure 4/e.

ATTENTION
See the instruction sheet provided with 
the  INSOL  /  MIXED  ZONE  kits  fro  con-
nection details.

CN10

Schedino 

INSOL/ZONA MIX e kit

alloggiamento scheda

CN10

COMUNICAZIONE

MODBUS

MODBUS 

 COMMUNICATION

1

23

45

6

Schedino 

INSOL/ZONA MIX e kit

alloggiamento scheda

Fig. 4/e

d

r

a

o

b

 

5

8

4

-

S

R

 

2

 

h

ti

w

 

r

e

li

o

B

d

r

a

o

b

 

5

8

4

-

S

R

 

1

 

h

ti

w

 

r

e

li

o

B

INSOL/MIXED ZONE
Expansion card

INSOL/ MIXED ZONE
Expansion card

Fig. 4/d

CN10

COMUNICAZIONE

MODBUS

MODBUS 

 COMMUNICATION

CONNETTORE CABLATO 

(cod. 6319173)

WIRED CONNECTOR

  

(cod 6319173)

1

23

45

6

1

2

3

DIP SWITCH

GESTIONE IN MODBUS
MODBUS MANAGEMENT

1 2 3

ON

INSTALLER PARAMETER SETTING:

PAR 16  

MODBUS ADDRESS

   

-- 

 = Not enabled

  

 

 

1...31 = Slave from 1 to 31

   

(ATTENTION:  Do  not  set  the 

slave  boilers  with  the  same 

address

PAR 17  

MODBUS CONFIGURATION

   

-- 

 = Not enabled

  

 

 

1...30 =  Default value: 25 

   

(See 

Table PAR 17 INST

)

Summary of Contents for Murelle Green Planet 110 HE I

Page 1: ...r and Service Instructions AUS WARNING The installation of this product must be carried out only by authorised personnel to the requirements of Australian Standard AS 5601 local authority gas elec tri...

Page 2: ...at the base Be physically capable Use personal protective equipment as appropriate e g gloves safety footwear During all manoeuvres and handling actions every attempt should be made to ensure the fol...

Page 3: ...that the flue pipe for the outlet of the products of the combustion is unobstructed and has been pro perly installed Make sure that any shutoff valves are open Make sure that the system is charged wit...

Page 4: ...2004 108 CE 2006 95 CE and 92 42 CE For optimum installation and operation always follow the instructions provided in this manual 1 DESCRIPTION OF THE BOILER 200 120 115 70 120 235 M R R3 S3 G 281 15...

Page 5: ...246 306 199 120 139 74 S3 R3 R M S1 G 600 Fig 1 a FIXTURES R Heating return G 1 1 2 UNI ISO 228 1 R3 D H W tank return G 1 1 2 UNI ISO 228 1 M Heating flow G 1 1 2 UNI ISO 228 1 G Gas connection G 3 4...

Page 6: ...ontinuous D H W flow rate t 30 C l min Minimum D H W flow rate l min D H W pressure min max bar D H W pressure min nom power bar Exhaust fumes temperature at max flow rate 80 60 C C 86 2 Exhaust fumes...

Page 7: ...Heating return sensor SR 4 Fan 5 Heating flow sensor SM 6 Safety thermostat 95 C 7 Exhaust probe SF 8 Primary heat exchanger 11 Water pressure transducer 12 Auto air vent 13 Pump 14 Drain vent 17 5 B...

Page 8: ...ENTS fig 3 KEY 1 Control panel 2 Fan 3 Ignition electrode 4 Primary heat exchanger 5 Ignition transformer 6 Exhaust probe SF 7 Auto Air Vent 8 Heating return sensor SR 9 Heating flow sensor SM 10 Safe...

Page 9: ...system must have the following installation parameters modified When the boiler is used in cascade PAR 1 of each boiler in the cascade must be reset as follows PAR 1 8 if boiler is NATURAL GAS G20 PAR...

Page 10: ...nated Master boiler to 0 On the Master boiler press any key to wake up the display Then press simultaneously the and the buttons for 5 seconds until the display is as shown Then press again simultaneo...

Page 11: ...acteristic impedance 100 GND GND GND GND GND GND INSTALLER PARAMETERS SETTING PAR 15 CASCADE ADDRESS Disabled 0 Master 1 7 Slave N B Ensure that each slave is numbered separately ATTENTION CONNECT UP...

Page 12: ...slave must be assigned with a different number PAR 17 MODBUS CONFIGURATION Disabled 1 30 Factory value 25 See Tab PAR 17 INST ATENTION Switch off and restart the boiler after setting PAR 17 1 1200 8...

Page 13: ...01 Boiler Hydraulic Parameter Par2 I R 0 199 Request CH zone 1 Enable DHW preparation Not used State CH zone 1 State preparation DHW State presence flame State presence alarm Setpoint CH zone 1 If you...

Page 14: ...RS 485 connection to the INSOL MIXED ZONE fig 4 e The RS 485 board can be connected to optional INSOL kit code 8092254 or MIXED ZONE code 8092252 Both require the board housing kit code 8092236 Carry...

Page 15: ...2 Filter on the gas pipe The gas valve is supplied ex factory with an inlet filter which however is not adequate to entrap all the impurities in the gas or in gas main pipes To prevent malfunctioning...

Page 16: ...the correct operation of the appliance set the installer para meter PAR 9 as indicated in TABLES 3 3 a see point 3 3 to access the instal ler parameters B type Fig 6 G N I N R A W When load loss of t...

Page 17: ...ting CO2 at the maximum and minimum capacity as specified in point 4 2 2 TABLE 2 Load loss PAR 9 mm H2O long chimneys 0 4 0 4 8 1 8 12 2 12 16 3 16 20 4 20 24 5 24 28 6 28 32 7 32 36 8 36 40 9 40 42 1...

Page 18: ...length PAR 9 exhaust m long chimneys 0 1 0 6 1 0 2 0 7 2 0 3 0 8 3 0 4 0 9 4 0 5 0 10 HORIZONTAL EXHAUST To ensure correct operation of the appliance do as follows set the installer parameter PAR 9 a...

Page 19: ...J h input 150 150 Other appliances up to 50 MJ h input 500 500 Appliances over 50 MJ h input and up to 150 MJ h input 1000 1000 n Appliances over 150 MJ h input 1500 1500 Unless appliance is certified...

Page 20: ...lu ded in the packaging NOTE Reset parameter 10 to 2 PAR 10 2 2 6 3 Remote control CR 73 connection optional The boiler is designed for connection to a remote control unit supplied on request code 809...

Page 21: ...2 environment thermostat SB Sensor tank L 2000 optional CR Remote control CR73 optional SE External sensor optional OP Programming clock optional AR Remote alarm VZ Zone valve AUX Auxiliary connection...

Page 22: ...code 8092228 or digital clock code 8092229 to program heating single zone only Fig 12 3 KEYS RESERVED FOR THE INSTALLER access to INST and OEM parameters PC CONNECTION To be used only with the SIME pr...

Page 23: ...azione corrente di ionizzazione in A 17 Visualizzazione portata sanitaria flussimetro es 18 l min e 0 3 l min o stato flussostato rispettivamente ON e OFF 12 Visualizzazione numero totale delle anomal...

Page 24: ...e codice errore ultima anomalia 61 Visualizzazione codice errore penultima anomalia 70 Codice di warning 90 Versione software presente su RS 485 es versione 01 91 Versione software presente su schedin...

Page 25: ...x100 0 1 from 0 1 to 19 9 0 0 1 from 20 to 81 9 Long chimneys 0 20 1 0 10 Remote control option setting 1 CR 73 1 2 CR 53 3 RVS 43 143 4 RVS 46 530 5 RVS 61 843 11 Correction values external sensor 5...

Page 26: ...lt values can be reset by setting PAR 49 1 and the PAR 1 and PAR 2 as specified at point 3 3 1 CODE DESCRIPTION E0 Operation in power reduction t between supply and return more than 40 C E1 External s...

Page 27: ...control CR 73 thermal regulator RVS connected to a mana gement card of a mixed zone MIXED ZONE code 8092234 card solar INSOL code 8092235 and to board RS 485 for managing up to 8 boilers in cascade or...

Page 28: ...rt up again 3 8 HEAD AVAILABLE TO SYSTEM fig 14 Residual head for the heating system is shown as a function of rate of flow in the graph in fig 14 Portata l h mbar 0 PREVALENZA 400 800 1200 778 748 73...

Page 29: ...as valve 2 Condensation drain trap 3 Heating return sensor SR 4 Fan 5 Heating Flow Sensor SM 6 Safety thermostat 95 C 7 Exhaust sensor SF 8 Primary heat exchanger 11 Water pressure transducer 12 Auto...

Page 30: ...all other gas ap pliances in the property working Combustion check 2 Connect the ue gas analyser to the ue gas sampling point as shown in the diagram Procedure for checking the combu stion Operate th...

Page 31: ...he fuel to propane G31 it is necessary to set SET 15 by pressing the key The standard display will automatically return after 10 seconds The table below shows the SET settings to enter when the type o...

Page 32: ...t be done During the routine service the condensa te drain can be checked by carefully pou ring water into the combustion chamber while the burner is removed Should the boiler not be used for long per...

Page 33: ...d by means of the installer parameter PAR 43 0 Not activated function 1 Curve setting A 2 Curve setting B 3 Curve setting A B The turning off of the function happens clicking on the button OFF return...

Page 34: ...circuit is intact check that there are no leaks HIGH WATER PRESSURE ERROR ALARM 03 fig 23 b If the pressure detected by the tran sducer is more than 4 8 bar the boi ler stops and the display shows er...

Page 35: ...tected the boiler will make two further attempts If circu lation is not detected it will stop and display ALL09 Note circulation is detected by a small rise in system pressure at the boiler transducer...

Page 36: ...Fig 23 t SOLAR COLLECTOR SENSOR ERROR S1 ALL 24 fig 23 18 When the solar probe is open or short circuited on the display the anomaly ALL 24 appears During this anomaly the boiler continues to function...

Page 37: ...e boiler stop and the display shows ALL 33 The boiler re start when the communi cation is restored or set PAR 16 Fig 23 j RS 485 COMUNICATION ERROR IN CASCADE MODE ALL 34 fig 23 x When il PAR 15 is di...

Page 38: ...not play with the appliance LIGHTING AND OPERATION BOILER IGNITION fig 24 The first ignition of the boiler must be carried out by qualified technical person nel Successively if it is necessary to star...

Page 39: ...d if low temperatures are expected to completely empty the hydraulic circuits to avoid pipes being damaged by frost ERRORS AND SOLUTIONS When there is a functioning error the display shows an alarm an...

Page 40: ...lashes on the display During such error the boiler conti nues normal functioning Fig 27 f ALL 20 Request assistance from quali fied technical personnel ALL 21 Request assistance from quali fied techni...

Page 41: ...ial Number refer to data plate Gas Type Natural Gas LPG Internal External Gas pressure Settings Central Heating Adjusted output setting Max Pa kW The System pipes MUST BE FLUSHED before the connecting...

Page 42: ...water Check gas ame is the correct colour and for gas and water leaks as the system heats up 12 Check that heat is going to all radiators through the manual or thermostatic rst and return via the lock...

Page 43: ...ettings 3 How to turn the heating system off in summer and on for winter 4 Where all the major items are their functions and how to check and turn them on or off Simple fault resolution i e power on 5...

Page 44: ...vice technician Name PIC Licence No Service Company Contact phone number Work Completed Note Service 3 year 5 Date Service technician Name PIC Licence No Service Company Contact phone number Work Comp...

Page 45: ...Contact phone number Work Completed Note Service 6 year 11 Date Service technician Name PIC Licence No Service Company Contact phone number Work Completed Note Service 7 year 13 Date Service technici...

Page 46: ...9 on each boiler must be set according to the calculated head loss tables on g 6 7 and 8 Boiler 1 Boiler 2 Boiler 3 Boiler 4 Boiler 5 Boiler 6 Calculated head loss Set value of PAR 9 PAR 1 see sec on...

Page 47: ...with gas isolated to ensure boiler fails safe Y N Turn on gas supply to boiler and isolate main burner disconnect gas valve and ensure boiler goes to lockout Y N Reset boiler lockout and retry ensuri...

Page 48: ...Cod 6316174 01 12 Documentation Dpt HUNT HEATING HYDRONIC SYSTEMS AUSTRALIA PTY LTD 11 Fiveways Boulevard Keysborough Victoria 3173 Telephone 1300 00 1800 Facsimile 9798 5133 www huntheat com au...

Reviews: