CONTROL SEQUENCE 

 
At the start of the freezing cycle, the contacts of 
the  magnetic  switch  mechanically  operated 
bythe actuator plate of the deflector cover are 
closed,  thereby  -  via  PC  board  -  closing  the 
circuit  to  the  main  contactor  coil  and 
consequently to the compressor and fan motors 
and 40" later, to the water pump motors. 
Then,  as  the  ice  thickness  reaches  the  value 
that corresponds to the full cube size, the film 
of water that constantly cascades over the slab 
of  ice  formed  on  the  evaporator,  arrives  to 
establish  a  contact  between  the  two  fingers 
(energized  at  low  voltage)  of  the  ice  sensor 
control, located on the front upper right side of 
the evaporator. If the contact between the two 
fingers of the ice sensor remains established - 
by the film of water – for more than 6 seconds, 
a  small  relay  of  the  PC  board,  get  energized, 
controlling  -simultaneously  both  the  harvest 
valve and the water drain valve. 
 

 

 
At this point, the unit initiates the defrost cycle. 
The  hot  gas  circulating  into  the  evaporator 
serpentine causes a slight melting of ice cubes 
which  get  released  from  their  molds.  Once 
entirely  released  the  ice  cubes  drop 
simultaneously into the ice storage bin below; 
by  doing  so  they  move  apart  from  the 
evaporator  bottom  end  the  plastic  deflector. 
This plastic deflector has on its side a magnetic 
switch that on account of the deflector swinging 
motion, caused by the ice while dropping in the 
bin, opens and closes their contacts. This will, 
in  turn,  deactivates  the  relay  contacts  that 
controls  the  hot  gas  and  water  drain  valve 
which get de-energized allowing the unit to start 
a new freezing cycle. 
When the ice bin is full of ice, the last batch of 
ice  cubes  released  from  the  evaporator 
accumulates  to  keep  the  bottom  end  of  the 
plastic  deflector  in  open  position;  with  the 
magnetic switch contacts open for longer than 
30'’ the entire unit stops with the glowing of the 
BIN FULL LED. 

 
The machine will restart when the ice deflector 
will  be  back  in  its  normal  vertical  position 
provided  that  3'  are  elapsed  from  unit  stop.  If 
not the machine will delay its restart till 3' are 
elapsed with the blinking of the BIN FULL LED. 
 

ALARM CONDITIONS 
 

 
 
 
 
 
 
 
 
 
 

Both  the  last  two  red  LED  are  on 
steady:  

Condenser Sensor out of order.

 

Both  the  last  two  red  LED  are 
blinking slow:  

Water error

Water  level  inside  the  water  sump 
too  slow  after  3'  or  6'  from  the 
activation of the Water Inlet Valve, 
according DIP Switch #4.. 
Both  the  last  two  red  LED  are 
blinking fast: 

Water error recovery

Every  30  minutes,  Water  inlet 
Solenoid  Valve  will  open  180 
seconds  for  recharge  water  after 
the  tripping  OFF  on  water  error,  If 
water  full,  the  machine  automatic 
reset. 

 

Reset mode

:  

Open  the  front  panel,  And  press 
MODE  button  can  go  to  start  up 
cycle. 

 
 
 
 
 
 
 

 

The fourth red LED is on steady:  

3 times too long Harvest Cycle 
time 

(according DIP Switch #3 

setup),  
The fourth red LED is blinking slow: 

Too Hi condensing temperature 
error. 

 The condenser sensor detected a 
temperature >70

℃.

 

For  the  first  2  times,  machine  will 
automatic  reset  when  temperature 
drop  down.  and  the  machine  will 
stop when high temperature occurs 
the third time, ice machine will stop, 

Reset mode:  

Open  the  front  panel,  And  press 
MODE button that can go to start up 
cycle. 
 
 

NOTE:

 in case of failure of ice level sensor, 

the  PC  Board  turns  -  on  automatically  the 
unit into the defrost cycle when the freezing 
cycle reaches 30 or 40 minutes according to 
the  operation  of  the  fan  motor  during  the 
freezing cycle. 

Summary of Contents for SVD 152

Page 1: ...SERVICE MANUAL SVD 152 222 22inch Model SVD 203 303 503 30inch Model Electronic Modular Cubers Part Number 73000009 00 Version A...

Page 2: ...LUMBER Conform to all applicable codes Water inlet 14 Drains 14 For the electrician Electrical connections 15 Final check list 16 START UP Start up cycle 17 Freezing cycle 17 18 Harvest cycle 18 OPERA...

Page 3: ...WIRING DIAGRAM SVD 152 222 29 SVD 203 303 30 SVD 503 220V 31 SVD 503 380V 32 SERVICE DIAGNOSIS 33 MAINTENANCE CLEANING INSTRUCTION Icemaker 34 Ice storage bin 34 Cabinet exterior 34 Cleaning Icemaker...

Page 4: ...3 SPECIFICATIONS MODULAR CUBER SVD 152 222 Ice Making Capacity...

Page 5: ...4 NOTE To keep your Modular cuber performing at its maximum capacity it is necessary to perform periodic maintenance as outlined on page 34 35 of this manual...

Page 6: ...5 SPECIFICATIONS MODULAR CUBER SVD 152 222...

Page 7: ...IFICATIONS MODULAR CUBER SVD 203 Ice Making Capacity NOTE To keep your Modular cuber performing at its maximum capacity it is necessary to perform periodic maintenance as outlined on page 31 of this m...

Page 8: ...7 SPECIFICATIONS MODULAR CUBER SVD 203...

Page 9: ...CIFICATIONS MODULAR CUBER SVD303 Ice Making Capacity NOTE To keep your Modular cuber performing at its maximum capacity it is necessary to perform periodic maintenance as outlined on page 31 of this m...

Page 10: ...9 SPECIFICATIONS MODULAR CUBER SVD303...

Page 11: ...CIFICATIONS MODULAR CUBER SVD503 Ice Making Capacity NOTE To keep your Modular cuber performing at its maximum capacity it is necessary to perform periodic maintenance as outlined on page 31 of this m...

Page 12: ...11 SPECIFICATIONS MODULAR CUBER SVD503...

Page 13: ...on nameplate 10 10 Extended periods of operation exceeding these limitations constitute misuse under the terms of Manufacturer s Limited Warranty resulting in a loss of warranty coverage SELECT LOCATI...

Page 14: ...he present one first remove the top panel from the lower machine Add a bead of food grade silicone sealant to the top edges of the lower units freezing compartment Lift the top machine onto the bottom...

Page 15: ...pressures Since water is the most important single ingredient in producing ice you cannot over emphasize the three items listed above Low water pressure below 1 bar may cause malfunction of the icema...

Page 16: ...ected ice maker location to be easily and prompt reached Undersized wiring or improperly installed electrical circuit will result in major problems and malfunctions Voltage variations should not excee...

Page 17: ...ompressor is snug on the mounting pads 8 Check all refrigerant lines and conduit lines to against vibration and possible failure 9 Has the cuber and the bin been wiped clean with clean damp cloths 10...

Page 18: ...on 6 In the meantime the condenser sensor starts to transmit the current to the PC Board keeping in operation the Fan Motor in ON OFF mode or continuously according to the condenser temperature 7 The...

Page 19: ...d and third cube harvest Check if size and shape combination is correct In areas where extreme problem water conditions exist filtering or purifying equipment is recommended 7 Check operation of magne...

Page 20: ...lve The thermostatic expansion valve meters how much liquid refrigerant is to be allowed into the evaporator section of the refrigeration system This is determined by the temperature of the TXV sensin...

Page 21: ...zing cycle forces the water to the top of the evaporator where it is distributed through a water tube and then cascades down the evaporator surface by gravity As it flows across the refrigerated evapo...

Page 22: ...be of the compressor WATER SYSTEM During the harvest cycle the electric water drain valve is energized thereby opening the drain line All water remained in the reservoir at the end of freezing cycle i...

Page 23: ...e When the ice bin is full of ice the last batch of ice cubes released from the evaporator accumulates to keep the bottom end of the plastic deflector in open position with the magnetic switch contact...

Page 24: ...l And press MODE button that can go to start up cycle Both the third yellow LED and forth red LED are blinking fast Ice thickness sensor fault When machine start if PC board detect the ice thickness O...

Page 25: ...k 6 and 30 every sixth cycle 6 OFF 7 ON Water pump work 30 every three cycles 6 ON 7 ON Water pump work 30 every six cycles 8 For factory use only 9 OFF Machine will stop after clean procedure need to...

Page 26: ...nt just before harvest Compressor amps experience a similar drop On water cooled the discharge pressure is constantly maintained during the freeze cycle by the water regulating valve However suction p...

Page 27: ...lug for transformer input and output power of two terminals for input power live line and compressor output of 3 terminals for power null line of one 5 PIN plug for components output 1 2 3 4 5 LEDNo 1...

Page 28: ...perature sensor probe located in contact with the condenser tube coil detects the condenser temperature variations and signals them by supplying current at low voltage to the P C BOARD In the air cool...

Page 29: ...the maximum level into the sump controlled by the Water Level Sensor After 3 minutes from the start up of the freezing cycle the Water Inlet Valve is energized again for a short period to re fill the...

Page 30: ...KNESS SENSOR E ICE FULL SENSOR F WATER LEVEL SENSOR G CONDENSER SENSOR H UIM BOARD AIR COOLED ONLY br brown b blue gy yellow green w white bk black r red o orange p purple g green y yellow I PC BOARD...

Page 31: ...mpressor contactor C Compressor D Ice thickness sensor E Ice full sensor F Water level sensor G Condenser temperature probe H Led display I PC Board J High pressure controller L Water pump M Water inl...

Page 32: ...essor contactor C Compressor D Ice thickness sensor E Ice full sensor F Water level sensor G Condenser temperature probe H Led display I PC Board J High pressure controller K Startup delay switch L Wa...

Page 33: ...terminal board B Compressor contactor C Compressor D Ice thickness sensor E Ice full sensor F Water level sensor G Condenser temperature probe H Led display I PC Board J High pressure controller K Sta...

Page 34: ...open Test and replace Compressor winding open Test and replace Machine runs makes ice does not try to harvest Ice thickness control open Check sensor fingers if are not covered with scale sediment To...

Page 35: ...sition for more that 30 should cause the ice maker to shut off Once the evaporator deflector is released in its closed position the ice maker will restart 8 Check cube size adjust if required through...

Page 36: ...the operation and blinking slow of the red Clean LED Push the CLEAN BUTTON when machine stop the machine restarts in the freezing cycle 9 ON Machine will go to freezing cycle directly 7 Replace the ev...