![SILENT KNIGHT INTELLIKNIGHT 5820XL Installation Manual Download Page 164](http://html1.mh-extra.com/html/silent-knight/intelliknight-5820xl/intelliknight-5820xl_installation-manual_1271114164.webp)
IntelliKnight 5820XL Installation Manual
9-2
151137
9.2
Ademco Contact ID Dialer Output
Table 9-2: Ademco Contact ID Output
Event Description
Event Family
Event
Qualifier
1=New,
3= Restore
Event Code Group #
Zone /
Contact ID #
Detector alarm.
Alarm
1
110
00
Zone
Detector alarm restore
Restore/Reset
3
110
00
Zone
Water flow switch alarm.
Alarm
1
113
00
Zone
Water flow switch alarm restore
Restore/Reset
3
113
00
Zone
Manual pull switch alarm.
Alarm
1
115
00
Zone
Manual pull switch alarm restore
Restore/Reset
3
115
00
Zone
Zone based, AUX1 switch alarm
Alarm
1
140
01
Zone
Zone based, AUX2 switch alarm
Alarm
1
140
02
Zone
Zone based, AUX1 switch alarm restore
Restore/Reset
3
140
01
Zone
Zone based, AUX2 switch alarm restore
Restore/Reset
3
140
02
Zone
System-based AUX1 switch alarm.
Alarm
1
140
01
000
System-based AUX2 switch alarm.
Alarm
1
140
02
000
System-based AUX1 switch alarm restore
Restore/Reset
3
140
01
000
System-based AUX2 switch alarm restore
Restore/Reset
3
140
02
000
Supervisory condition
Trouble
1
203
00
Zone
Supervisory restore
Trouble
3
203
00
Zone
Checksum error.
Trouble
1
300
00
000
AC power lost
Trouble
1
301
00
000
AC power restore
Trouble
3
301
00
000
Battery voltage low
Trouble
1
302
Exp ID
000
Battery voltage restore
Trouble
3
302
Exp ID
000
Initial Power Up.
Trouble
1
305
00
000
Ground fault condition detected
Trouble
1
310
Exp ID
000
Ground fault condition restore
Trouble
3
310
Exp ID
000
Aux Power Trouble
Trouble
1
320
00
000
Aux Power Trouble Restore
Trouble
3
320
00
000
Notification output trouble
Trouble
1
320
00
Group #
Notification output trouble restore
Trouble
3
320
00
Group #
SLC Class A supervision lost
Trouble
1
331
Exp ID
000
SLC Class A supervision restored
Trouble
3
331
Exp ID
000
Short detected on SLC communication loop
Trouble
1
332
Exp ID
000
Short removed from SLC communication loop
Trouble
3
332
Exp ID
000
SBUS expander trouble
Trouble
1
333
Exp ID
000
SBUS expander trouble restore
Trouble
3
333
Exp ID
000
SBUS Class A supervision lost
Trouble
1
333
Exp ID
000
Summary of Contents for INTELLIKNIGHT 5820XL
Page 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Page 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Page 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Page 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Page 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Page 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Page 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Page 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Page 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...