System Operation
151137
8-7
8.4.9
Reset alarms
Press
and enter your code or rotate the key at the prompt. If an external reset switch
has been installed, activating the switch will reset alarms. If you are already using system
menus when you press
, you will not need to enter your code or rotate the key.
8.4.10
Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in
compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL
TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an
out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report
(“373” + Zone # for Contact ID format; “FT” + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below. Section 8.4.17
provides instructions for printing the status of all detectors in the system.
1. From the User or Installer Menu, press
for Point Functions.
2. Press
for Point Status.
3. Select the module where the point you want to check is located.
4. Enter the number of the point you want to check and press
.
5. A screen similar to those shown in Figure 8-4 will display.
Figure 8-4 Checking Detector Sensitivity Compliance
If a printer is attached to the system (via a Module 5824 Serial/Parallel Interface), you can
print detector status (see Section 8.4.17).
R E S E T
R E S E T
2
2
E N T E R
Summary of Contents for INTELLIKNIGHT 5820XL
Page 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Page 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Page 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Page 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Page 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Page 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Page 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Page 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Page 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...