Programming
151137
7-37
7.5.6
Miscellaneous Options
Through this programming option you can set the water flow delay time, low AC report delay,
enable or disable automatic daylight savings time adjustment, clock format, and AC clock
frequency.
7.5.6.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction
with a water flow switch. The delay is system-wide. All water flow switches on the system
will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Press
or
to display the installer menu.
3. Select
for Program Menu.
Display reads:
,QLWLDOL]LQJ
3OHDVHZDLW
4. Select
for System Options.
5. Select
for Miscellaneous Options.
A screen similar to the one shown in Figure 7-18 will display.
Figure 7-18 Water Flow Delay Programming Screen
6. Enter the number of seconds (0 to 90 ) to delay an a water flow switch alarm, then press
.
7
5
6
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
Summary of Contents for INTELLIKNIGHT 5820XL
Page 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Page 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Page 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Page 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Page 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Page 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Page 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Page 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Page 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...