System Operation
151137
8-9
8.4.16
Communicating with a Remote Computer
An installer at the panel site can initiate communications between the panel and a computer
running the SK Analog Fire System Editor 5590. You can use this feature to upload a panel
configuration. For example, if you have made programming changes to an installation on site
using an annunciator, you can send your changes to the computer, so that the central station
will have the latest data about the installation. Refer to the 5590 manual (P/N 151004) for
complete details about communication hardware set-up. To initiate communication, follow
the steps below.
1. From the Installer Main Menu, select
for Up/Download.
2. From the next screen that displays, select the communication device. Options are:
3. If you are using the panel’s internal modem to communicate, you will be prompted to
enter a phone number. If you are communicating via the RS232 connection, a phone num-
ber is not needed and this step will be skipped.
If the phone number you will be calling is already displayed, press
. Continue with
Step 4.
If the phone number you will be calling is not already displayed, enter the number and press
. The number you enter will become the default phone number. A phone number can
be up to 40 digits long and can contain the following special characters.
Use the number buttons on the annunciator or the up- and down-arrow keys to select special
characters. Characters begin displaying after “9”.
4. You will be prompted to enter an account number. If the account number you want to use
is already displayed, just press
to begin communication.
If the account number displayed is not the correct one, enter the account number and press
to begin communication. The number you enter will become the default account
number.
5. The panel will attempt to communicate with the computer. If communication was estab-
lished, the upload task you created will be placed on the 5590 job queue, awaiting process-
ing. When processing is completed, an “Unsolicited Upload” task will appear in the
queue.
Important!
To ensure proper downloading, make sure that the SK Analog Fire System Editor’s revision is equal to or
greater than the software revision of the control panel. See Section 8.4.14.
= Internal Modem
If you select this option, you will use the panel’s built-in modem to call
the panel.
= RS232 connection
If you select this option, the panel and a computer are both on-site
connected via a 9-pin straight-through serial cable.
#
Pound (or number) key on the telephone
*
Star key on the telephone
,
Comma (character for 2-second pause)
9
1
2
E N T E R
E N T E R
E N T E R
E N T E R
Summary of Contents for INTELLIKNIGHT 5820XL
Page 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Page 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Page 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Page 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Page 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Page 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Page 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Page 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Page 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...