![SILENT KNIGHT INTELLIKNIGHT 5820XL Installation Manual Download Page 15](http://html1.mh-extra.com/html/silent-knight/intelliknight-5820xl/intelliknight-5820xl_installation-manual_1271114015.webp)
Before You Begin Installing
151137
3-3
3.4
Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with
telephone communication or cause false alarms. To avoid induced noise, follow these
guidelines:
•
Isolate input wiring from high current output and power wiring. Do not pull one multi-
conductor cable for the entire panel. Instead, separate the wiring as follows:
•
Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to earth ground at the panel. You must route high and low voltages separately.
•
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit
board where it could induce noise into the sensitive microelectronics or pick up unwanted
RF noise from the high speed circuits. See Figure 3-1 for an example.
•
High frequency noise, such as that produced by the inductive reactance of a speaker or
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it
around a ferrite toroid.
33
SC-
L1
SLC OUT
SLC terminals
32 VDC
150 mA
34
SC+
35
SC-
L2
SLC IN
Used for Class A installations
36
SC+
37
Ring
Phone Line 1 Telco Ring
N/A
38
Tip
Phone Line 1 Telco Tip
39
Ring
Phone Line 1 Premises Ring
40
Tip
Phone Line 1 Premises Tip
41
Ring
Phone Line 2 Telco Ring
N/A
42
Tip
Phone Line 2 Telco Tip
43
Ring
Phone Line 2 Premises Ring
44
Tip
Phone Line 2 Premises Tip
45
SC-
SLC Programming Terminal
( - )
32 VDC
150 mA
46
SC+
SLC Programming Terminal
( + )
32 VDC
150 mA
High voltage
AC power, Terminals 1-3
SLC loops
Terminals 33-36
Audio input/output
Phone line circuits, Terminals
37-44
Notification circuits
Terminals 4-15
SBUS Terminals
16-23
Relay circuits
Terminals 24-32
Table 3-1: Terminal Strip Description and Electrical Rating
Terminal # and Label
Description
Rating
Voltage
Current
Summary of Contents for INTELLIKNIGHT 5820XL
Page 16: ...IntelliKnight 5820XL Installation Manual 3 4 151137 Figure 3 1 Wire Routing Example ...
Page 24: ...IntelliKnight 5820XL Installation Manual 3 12 151137 ...
Page 68: ...IntelliKnight 5820XL Installation Manual 4 44 151137 ...
Page 82: ...IntelliKnight 5820XL Installation Manual 5 14 151137 ...
Page 104: ...IntelliKnight 5820XL Installation Manual 6 22 151137 ...
Page 148: ...IntelliKnight 5820XL Installation Manual 7 44 151137 ...
Page 162: ...IntelliKnight 5820XL Installation Manual 8 14 151137 ...
Page 172: ...IntelliKnight 5820XL Installation Manual 9 10 151137 ...
Page 178: ...IntelliKnight 5820XL Installation Manual 10 6 151137 ...