Communication via
CAN bus (CANopen)
MSA501
Date: 12.10.2018
Art. No. 88734
Mod. status 330/18
Page 38 of 51
Subindex
03h
Description
Inhibit time (function is not supported, only compatibility entry for various
configurators)
Access
ro
PDO-Mapping
no
Data type
UNSIGNED 16
Default
0h
EEPROM
no
Sub-index
04h (is not used, access attempt generates error message)
Subindex
05h
Description
Event timer für TPDO1 hard-wired (CiA DS-406) mit cyclic timer 6200h
Access
rw
PDO-Mapping
no
Data type
UNSIGNED 16
Default
0h
EEPROM
yes
Data content
The service is disabled by writing the value 0h. The content of this object is
identical with object 6200h. If the value is changed with the timer
running, the change will be applied only with the next timer operation.
Subindex
06h (is not used, access attempt generates error message)
5.6.2.19
1801h: 2nd Transmit PDO Parameter
TPDO2 is used for synchronous PDO transmission according to CiA DS-406.
The communication parameters for TPDO2 are set via object 1801h.
Subindex
00h
Description
indicates the largest supported sub-index
Access
ro
PDO-Mapping
no
Data type
UNSIGNED 8
Default
5h
EEPROM
no