7 Assembly/Installation
7.1 Check Contents of Delivery
Ensure that the contents of the delivery are complete and intact. See chapter 1.3 Contents of
Delivery.
INFORMATION
On receipt and before initial use, check the device for damage. If the
device is damaged, contact our customer service and do not install the
device in your system.
Damaged components can disrupt or damage the system.
7.2 Installation
The device’s power loss can reach up to 25 Watts. The loss from each of the TPs used must
also be added. To ensure the required air circulation for cooling, the mounting instructions for
the PIM, as well as the corresponding TPs must be followed!
To dissipate the waste heats from the device, the clearance between the heatsink of the PIM
and the back wall should be at least 45 mm.
The specified installation clearances may be reduced if appropriate measures and technical
precautions are taken to dissipate the generated waste heat of all connected components
(e.g. displays).
For this device, no other special installation guidelines apply. However, the installation
guidelines for the TPs of connected components must be observed.