4.2 Electrical Requirements
Supply voltage
+24 V DC ±20 % (SELV/PELV)
UL: Class 2 or LVLC
Protection class
III
Current consumption of the
voltage supply (+24 V)
without TP
typically 600 mA
(with no external devices
connected)
maximum 1100 mA
(with external devices connected)
Current consumption of the
voltage supply (+24 V)
with TP
For the total current consumption, the current consumption of this PIM
must be added to that of the TP used. The current consumption
specifications for the TP used can be found in the module-specific
operating manual
Inrush current with 24 V/10 A
fixed voltage supply
maximum 2.5 A (for 2 ms, load-dependent)
Inrush current without current-
limiting supply
maximum 3.3 A (for 6 µs, load-dependent)
INFORMATION
For USA and Canada:
The supply must be limited to:
a) max. 5 A at voltages from 0-20 V DC, or
b) 100 W at voltages from 20-60 V DC
The limiting component (e.g. transformer, power supply or fuse) must be
certified by an NRTL (Nationally Recognized Testing Laboratory).
Page 12