The mechanical dimensions of the module carrier and the fastening on the mounting plate
of the cabinet above are:
A
depends on the selected module carrier
100 mm for MDM 011
160 mm for MDM 021
220 mm for MDM 031
280 mm for MDM 041
The cable ducts below must be placed with a minimum distance of 10 mm to the module
carrier.
The cable duct above must be placed with a distance of 40 mm to the module carrier. This
is necessary to get enough air through the heat sink.
The specified installation clearances can be reduced under some conditions. Provided that
the appropriate measures and technical precautions are taken to dissipate the heat gener-
ated from loss.
Fastening material:
4 hexagon socket screws to DIN 912, M5
Tool required:
4 mm Allen key -