Performance Level e, Category 4 or SILCL 3
– Conventional
To meet the requirements of safety category 4, performance level "e" for EN ISO 13849-1
and SILCL 3 according to EN / IEC 62061, the placement of the lines must comply with EN
ISO 13849-2, table D.4 (separate placement, prohibiting of error via short circuits between
wires) as cross-circuit detection is not possible here.