background image

8

5. Fire Alarm Activation Input

  The 

“FIRE”

 input is used to activate the siren in the event of a fire alarm. It is activated by  

  applying a voltage of +12 V and the siren sounds with a special fire detection sound.

  

Attention!

   

If the “TRIGER” and “FIRE” input are activated at the same time, the “FIRE” input  

   

will have priority

6. Bypassing the Siren’s Tamper - Removing the Lid 

 

“TC”

 input (Tamper Control input) is used to deactivate the siren’s Tamper, when you open the

  cover of the siren for service, without given an alarm. Connect “TC” input to a “PGM” output of

  the alarm control panel, which provides 12 V at standby mode and goes to 0 when the panel

  arm. The presence of 12V on this input disables the Tamper of the siren for 10 minutes. 
 

 

In the Sigma Alarm panels, connect the siren’s TC input to a PGM, which must be 

    programmed as type 27.

7. Visual or audible indication input 

  The 

“SIGN”

 input is used when we want to have visual and / or audible indication of arming or  

  disarming the panel via the siren when, arming or disarming the system by remote control. It is  

  activated as long as there is +12 V at its input and is connected to a programmable output of  

  the panel (PGM) which is programmed accordingly.
 

 In the Sigma Alarm panels, it must be connected to a PGM programmed as type 29.

8. Fault Output

  The siren automatically monitors the battery status (Battery Self-Test) by dynamically testing  

  the battery, every hour when there is a voltage at the siren power input (+ 12V-) or, every five  

  minutes when there is no voltage. If, during the test, the battery voltage is lower than 11.5V,  

  we have a low battery voltage indication, and if the battery voltage is below 10.0V, we have a  

  battery failure indication. In both cases, the “FLT OUT” (Fault Output) output is activated.

  The “FLT OUT” output is  0V and becomes Open Collector (OC) when the battery voltage is  

  low or the battery is damaged. Returns to standby again at the next test and if the battery volt 

  age rises above 11.5V or the battery is replaced with a new one.

  This notifications are used to inform the user and / or the Central Monitoring Station, the 

  battery status of the system. A LED may be connected to this output or it may be connected to  

  the control panel, as shown in the siren wiring schematic.
 

 

For greater security, program the Control panel zone as a 24-hour EOL and connect the  

    terminal resistor in the siren.

9. Alarm Output

  The

 “ALR OUT” (Alarm)

 output is activated when the siren triggers an alarm if its power supply  

  voltage from the Alarm panel is interrupted, or the foam, shock or 3-axis detector is activated.   

 The 

“ALR OUT”

 is activated simultaneously with the siren and is 0 at standby and becomes  

  Open Collector (OC) on activation. Used to update the system user and notify the Central  

  Monitoring Station for this event. You can connect it to a LED indicator or a zone of the panel,  

  programmed accordingly, as shown in the schematic that displays the siren connection.
 

 

For more safety, program the zone as EOL and place the EOL resistor of this zone inside  

      the  box of the siren.

Summary of Contents for IRIS PLUS

Page 1: ...1 INSTALLATION MANUAL IRIS PLUS Outdoor self powered siren...

Page 2: ...o protect the battery from overcharging It has short circuit protection on the battery charging of the cables output Also it has overcurrent and short circuit protection for the battery with simultane...

Page 3: ...and foam detector and then you can open the cover of the siren to change the battery or make service without the siren sound The built in FLASH has five high brightness and low power LEDs which are sh...

Page 4: ...tage on this input drops bellow 5 8 V DC Activation from Trigger It is balanced when there are 0VDC on the Trigger input It sounds an alarm if the voltage of power supply is interrupted or if the volt...

Page 5: ...ACTIVATION INPUT 12V FOR FIRE ALARM SIGN INPUT 12V FOR AUDIBLE AND VISUAL VERIFICATION OF THE CONTROL PANEL STATUS TC INPUT 12V FOR TAMPER 3 AXIS ACCELEROMETER AND FOAM DETECTOR CANCELATION FLT OUT LO...

Page 6: ...nect the siren to the panel as explained in the connection terminals on page 5 and the following wiring diagram 6 When you finish cable connections connect the battery to the siren The siren can remai...

Page 7: ...emain open for only 10 seconds and then be deactivated If a fault is detected on the battery the FLT OUT output will remain activated after the end of 10 seconds and until the fault is restored Once t...

Page 8: ...here is a voltage at the siren power input 12V or every five minutes when there is no voltage If during the test the battery voltage is lower than 11 5V we have a low battery voltage indication and if...

Page 9: ...siren will follow If all the LEDs are off then the siren will have no lighting at standby mode To store this setting into memory press the MENU button The LED with the indication L S will turn on Sele...

Page 10: ...twenty four hours the duration of each alarm should be longer than 20 seconds Each time you press SELECT button you will hear the sound of the siren and will turn on or turn off all five LEDs of the...

Page 11: ...urns to standby mode after three minutes without pressing any of the two buttons This function allows you to open the siren for maintenance or to change the battery without the siren being activated b...

Page 12: ...e battery voltage is lower than this replace the battery and connect the new battery keeping in mind to use the correct polarity 4 Check for signs of water or insects entering the siren and clean if n...

Reviews: