background image

1

INSTALLATION MANUAL

IRIS PLUS

Outdoor self powered siren

Summary of Contents for IRIS PLUS

Page 1: ...1 INSTALLATION MANUAL IRIS PLUS Outdoor self powered siren...

Page 2: ...o protect the battery from overcharging It has short circuit protection on the battery charging of the cables output Also it has overcurrent and short circuit protection for the battery with simultane...

Page 3: ...and foam detector and then you can open the cover of the siren to change the battery or make service without the siren sound The built in FLASH has five high brightness and low power LEDs which are sh...

Page 4: ...tage on this input drops bellow 5 8 V DC Activation from Trigger It is balanced when there are 0VDC on the Trigger input It sounds an alarm if the voltage of power supply is interrupted or if the volt...

Page 5: ...ACTIVATION INPUT 12V FOR FIRE ALARM SIGN INPUT 12V FOR AUDIBLE AND VISUAL VERIFICATION OF THE CONTROL PANEL STATUS TC INPUT 12V FOR TAMPER 3 AXIS ACCELEROMETER AND FOAM DETECTOR CANCELATION FLT OUT LO...

Page 6: ...nect the siren to the panel as explained in the connection terminals on page 5 and the following wiring diagram 6 When you finish cable connections connect the battery to the siren The siren can remai...

Page 7: ...emain open for only 10 seconds and then be deactivated If a fault is detected on the battery the FLT OUT output will remain activated after the end of 10 seconds and until the fault is restored Once t...

Page 8: ...here is a voltage at the siren power input 12V or every five minutes when there is no voltage If during the test the battery voltage is lower than 11 5V we have a low battery voltage indication and if...

Page 9: ...siren will follow If all the LEDs are off then the siren will have no lighting at standby mode To store this setting into memory press the MENU button The LED with the indication L S will turn on Sele...

Page 10: ...twenty four hours the duration of each alarm should be longer than 20 seconds Each time you press SELECT button you will hear the sound of the siren and will turn on or turn off all five LEDs of the...

Page 11: ...urns to standby mode after three minutes without pressing any of the two buttons This function allows you to open the siren for maintenance or to change the battery without the siren being activated b...

Page 12: ...e battery voltage is lower than this replace the battery and connect the new battery keeping in mind to use the correct polarity 4 Check for signs of water or insects entering the siren and clean if n...