Model 3100 Series Flame Detector (11/04)
Page: 15
Instruction Manual
APPENDIX B
TABLES
B.1 Dip Switch Settings
B.1.1
Sensitivity
Sensitivity
SW1
SW2
Level
20 Foot
ON
ON
4
40 Foot
OFF
ON
3
60 Foot
ON
OFF
2
80 Foot
OFF
OFF
1
B.1.2
Verify Control (3100-02, -03, -04 and -05 Models only)
Verify
Description
SW3
SW4
SW5
Level 0
Verify = Fire
OFF
OFF
OFF
Level 1
Min. Verify (shorter)
ON
OFF
OFF
Level 2
Min. Verify (shorter)
OFF
ON
OFF
Level 3
Min. Verify (shorter)
ON
ON
OFF
Level 4
Min. Verify (shorter)
OFF
OFF
ON
Level 5
Min. Verify (shorter)
ON
OFF
ON
Level 6
Max. Verify (longer)
OFF
ON
ON
Level 7
Verify Disabled
ON
ON
ON
B.1.3
Fire Output“Latching” Control
Fire Output
Description
SW6
Latching
Alarm until Power down Reset
OFF
Following
Alarm until no fire (.5 to 10 sec.)
ON
B.1.4
Verify Relay “Latching” Control (3100-02, -03, -04 and -05 Models only)
Verify Relay
Description
SW7
Latching
Alarm until Power down Reset
OFF
Following
Alarm until no fire (.5 to 10 sec.)
ON
B.1.5
Detector "Non-Latching" Control
SW6, SW7 and SW8 must be on for the detector to be "Non-Latching".
B.1.6
Factory Use Only
SW8 and SW9 must be in the
OFF
position
for normal operation. They are used for factory
calibration and testing.