4.7.7 Terminate single-phase cable
1. Feed the single-phase cable through the gland.
Note:
When terminating the 3-core cable, do not
terminate the Earth to common chassis Earth terminal.
This core will be used for the IMI reference point.
2. Strip and apply bootlaces to the cable if stranded, no
bootlace if solid core.
3. Insert the cable into the designated field wiring terminals
to the top-left of the connection box.
Note:
For internal wiring, brown denotes 230VAC line
and blue denotes 230VAC neutral.
4. Close the hatch and tighten all cover screws to 2Nm.
4.7.8 Terminate Ethernet cable
1. Unscrew the Ethernet IP connector from the HMI screen.
2. Slide housings mating half over the Ethernet cable
coming from the conduit.
Note:
Ensure that the housing does not slide all the way
back into the conduit.
3. Terminate the Ethernet cable into the Cat 6A toolless jack
from the installation kit using Mode A.
Note:
Ensure that you connect shield to equipment
ground on both the IPU and UU ends.
Figure 20: Cat6A toolless.
4. Slide the housing cover back up over the jack, as shown
in
.
Figure 21: Terminated Ethernet jack.
5. Remove and discard Female to Female inline connector
from housing.
6. Connect Ethernet cable from the HMI and close the
housing.
Note:
Make sure that the housing is tightened in the
middle and at the two end nuts to ensure a waterproof
seal.
VersiCharge Ultra 175™ kW Fast Charger |
Site Installation Manual