1. Strip, bootlace (only if stranded wire, skip bootlace if
solid core), and insert the wires into the field wiring
terminals as follows:
Terminal
Wire
2
• User Unit 230 VAC Neutral
7
• User Unit 230 VAC Line
18
• User Unit 24V Safety Loop
19
• User Unit 24V Safety Loop
22
• IMI Earth reference (from supply)
• IMI Earth reference (to user unit)
11
• (optional) upstream breaker shunt output,
230 VAC Line
4
• (optional) upstream breaker shunt output
230 VAC Neutral
2. Locate the Ethernet cable from the control shelf and use
the toolless jack from the installation kit to terminate
the Cat 6A cable.
Note:
Use colour code A for all Cat cable connections.
3. Cover the Ethernet jack in heat shrink and secure to the
frame of the IPU.
4. Connect a 1m patch lead from the Ethernet jack to the
control shelf.
Note:
Alternatively, terminate the cable directly with a
male connector and insert this into the control shelf.
Figure 13: Cat 6A toolless, Example Ethernet Terminations