Analogue Input Blocks, PROFIBUS
4.2 Analogue Input Blocks (PA Slot 1 & 2) Parameter List, PROFIBUS
SITRANS TH400 PROFIBUS® PA
46
Configuration Manual, 02/2007, A5E01039143-01
Parameter
Rel.
Index Description
Type
Store Size
byte
RO /
R/W Min. Max. Default
HI_LIM
23
Value for the upper limit of warnings.
Float
SRC 4
R/W
Max
value
LO_LIM
25
Value for the lower limit of warnings.
Float
SRC 4
R/W
Min
value
LO_LO_LIM
27
Value for the lower limit of alarms.
Float
SRC 4
R/W
Min
value
HI_HI_ALM
30
State of the upper limit of alarms.
DS-39
D
16
RO
0
HI_ALM
31
State of the upper limit of warnings.
DS-39
D
16
RO
0
LO_ALM
32
State of the lower limit of warnings.
DS-39
D
16
RO
0
LO_LO_ALM
33
State of the lower limit of alarms.
DS-39
D
16
RO
0
SIMULATE
34
For commissioning and test purposes the input value from the
Transducer Block in the Analogue Input Function Block AI-FB
can be modified. This means that the Transducer and AI-FB will
be disconnected.
DS-50
SRC 6
R/W
Disable
d
OUT_UNIT_TEXT
35
If a specific unit of OUT parameter is not in the code list the user
has the possibility of writing the specific text in this parameter.
The unit code is then equal to ”textual unit definition”.
Octet
string
SRC 16
R/W
-