The Transducer Block
3.6 Transducer Block Examples Setup
SITRANS TH400 PROFIBUS® PA
Configuration Manual, 02/2007, A5E01039143-01
21
3.6.11
Measurement of voltage (linear) with two sensors:
PRIMARY_VALUE_UNIT
= µV, mV or V
LIN_TYPE
= No linearisation
LIN_TYPE_2
= No linearisation
SENSOR_MEAS_TYPE
= Anything, but not "PV = SV_1, SV_2 not available"
SENSOR_CONNECTION
= N/A (ignored in setup check)
SENSOR_CONNECTION_2
= N/A (ignored in setup check)
RJ_TYPE
= N/A (ignored in setup check)
Connections:
2 x mV
1
2
+
+
-
-
Connections with two sensors can be
configured for
2 measurements, difference, average
or redundancy
3.6.12
Measurement of 2 potentiometers (with Linear interpolation linearisation):
PRIMARY_VALUE_UNIT
= %
LIN_TYPE
= Table Linearisation
LIN_TYPE_2
= Table Linearisation (same table as sensor 1)
SENSOR_MEAS_TYPE
= Anything, but not "PV = SV_1, SV_2 not available"
SENSOR_CONNECTION
= Default set to 3-wire
SENSOR_CONNECTION_2
= Default set to 3-wire
RJ_TYPE
= N/A (ignored in setup check)
Connections:
2 x 3-wire potmeters
Connections with two sensors can be
configured for
2 measurements, difference, average
or redundancy
The coordinates (x,y) describing the linear interpolation linearisation must be entered in
PR_CUST_LIN Block (PA Slot 4). See 3.9.2 Linear Interpolation Linearisation, Paramter List
for further details.