The Transducer Block
3.6 Transducer Block Examples Setup
SITRANS TH400 PROFIBUS® PA
20
Configuration Manual, 02/2007, A5E01039143-01
3.6.9
Measurement of potentiometer (linear) with two sensors:
PRIMARY_VALUE_UNIT
= %
LIN_TYPE
= No linearisation
LIN_TYPE_2
= No linearisation
SENSOR_MEAS_TYPE
= Anything, but not "PV = SV_1, SV_2 not available"
SENSOR_CONNECTION
= Default set to 3-wire
SENSOR_CONNECTION_2
= Default set to 3-wire
RJ_TYPE
= N/A (ignored in setup check)
Connections:
2 x 3-wire Potmeters
Connections with two sensors can be
configured for
2 measurements, difference, average
or redundancy
3.6.10
Measurement of voltage (linear) with one sensor:
PRIMARY_VALUE_UNIT
= µV, mV or V
LIN_TYPE
= No linearisation
LIN_TYPE_2
= N/A (ignored in setup check)
SENSOR_MEAS_TYPE
= PV = SV_1, SV_2 not available
SENSOR_CONNECTION
= N/A (ignored in setup check)
SENSOR_CONNECTION_2
= N/A (ignored in setup check)
RJ_TYPE
= N/A (ignored in setup check)
Connections:
mV
+
-