The Transducer Block
3.8 AI_TRANSDUCER Block (PA Slot 3) Parameter List
SITRANS TH400 PROFIBUS® PA
32
Configuration Manual, 02/2007, A5E01039143-01
3.8.6
Diagnostic parameters
Parameter
Rel.
Index
PA
Description
Type
Store
Size
byte
RO /
R/W
Min.
Max.
Default
INPUT_FAULT_GEN
24
Input malfunction: Diagnosis object for errors that concern all
values
0 =
device OK
Bit:
0 =
RJ error
1 =
Hardware error
2 – 4 =
reserved
5 – 7 =
manufacturer-specific
Unsigned
8
D
1
RO
0
INPUT_FAULT_1
25
Input malfunction: Diagnosis object for errors that concern SV_1
0 =
Input OK
Bit:
0 =
underrange
1 =
overrange
2 =
lead breakage
3 =
short circuit
4 – 5 =
reserved
6 – 7 =
manufacturer-specific
Unsigned
8
D
1
RO
0
INPUT_FAULT_2
26
Input malfunction: Diagnosis object for errors that concern SV_2
0 =
Input OK
Bit definition see INPUT_FAULT_1
Unsigned
8
D
1
RO
0
RJ_FAULT
67
Input malfunction: Diagnosis object for errors that concern RJ
sensor.
0 =
Input OK
Bit:
0 =
underrange
1 =
overrange
2 =
lead breakage
3 =
short circuit
Unsigned
8
D
1
RO
0
HW_ERROR
86
Diagnostic bit value indicating hardware status
0 =
hardware OK
Bit:
0 =
Input power supply error
1 =
Input initialisation error
2 =
Input communication error
3 =
Internal temperature sensor error
4 =
Device not factory calibrated
5 – 6 =
reserved
7 =
Watchdog initiated cold start occurred
Unsigned
8
D
1
RO
0