The Transducer Block
3.8 AI_TRANSDUCER Block (PA Slot 3) Parameter List
SITRANS TH400 PROFIBUS® PA
28
Configuration Manual, 02/2007, A5E01039143-01
3.8.2
RTD / Resistor specific parameters
Parameter
Rel.
Index
PA
Description
Type
Store Size
byte
RO /
R/W Min. Max. Default
SENSOR_CONNECTION 36
Connection to sensor 1, select for 2-, 3- and 4-wire connection.
Ignored if sensor 1 is not a resistive sensor.
Defined codes:
0 =
2 wires
1 =
3 wires
2 =
4 wires
Unsigned
8
SRC 1
R/W
1
COMP_WIRE1
37
Value in OHM to compensate line resistance when
Sensor 1 is a resistive sensor, connected with 2 wires.
Float
SRC 4
R/W
0
100 0
COMP_WIRE2
38
Value in OHM to compensate line resistance when
Sensor 2 is a resistive sensor, connected with 2 wires.
Float
SRC 4
R/W
0
100 0
SENSOR_
CONNECTION_2
62
Connection to sensor 2, select for 2-, 3- and 4-wire connection.
Ignored if sensor 2 is not a resistive sensor.
Defined codes:
0 =
2 wires
1 =
3 wires
Unsigned
8
SRC 1
R/W
0
CABLE_RES1
87
For 3- or 4-wire resistance measurements.
Indicates the measured cable resistance in the wire connected to
terminal 3. For 3-wire measurements it is multiplied by 2
Float
D
4
RO
0,0
CABLE_RES2
88
For 4-wire resistance measurements.
Indicates the measured cable resistance in the wire connected to
terminal 6.
Float
D
4
RO
0,0
RTDX_FACTOR_1
89
Indicates the X factor for custom defined PtX, NiX, CuX for
LIN_TYPE
Unsigned
16
SRC 2
R/W
100
RTDX_FACTOR_2
90
Indicates the X factor for custom defined PtX, NiX, CuX for
LIN_TYPE_2
Unsigned
16
SRC 2
R/W
100