The Transducer Block
3.8 AI_TRANSDUCER Block (PA Slot 3) Parameter List
SITRANS TH400 PROFIBUS® PA
Configuration Manual, 02/2007, A5E01039143-01
27
Parameter
Rel.
Index
PA
Description
Type
Store Size
byte
RO /
R/W Min. Max. Default
242 =
Custom-defined RTD PtX a=0.003850 (X factor of Pt1)
243 =
Custom-defined RTD NiX a=0.006180 (X factor of Ni1)
244 =
Custom-defined RTD CuX a=0.004270 (X factor of Cu1)
245 =
Custom-defined RTD PtX a=0.003916 (X factor of Pt1)
UPPER_SENSOR_LIMIT 21
Physical upper limit function of sensor1 (e.g. Pt 100 = 850°C) and
input range.
The unit of UPPER_SENSOR_LIMIT is the
PRIMARY_VALUE_UNIT.
Float
N
4
RO
850
LOWER_SENSOR_LIMIT 22
Physical lower limit function of sensor1 (e.g. Pt 100 = -200°C) and
input range.
The unit of LOWER_SENSOR_LIMIT is the
PRIMARY_VALUE_UNIT.
Float
N
4
RO
-200
LOWER_SENSOR_
LIMIT_2
63
Physical lower limit function of sensor2 (e.g. Pt 100 = -200°C) and
input range.
The unit of LOWER_SENSOR_LIMIT is the
PRIMARY_VALUE_UNIT.
Float
N
4
RO
-200
UPPER_SENSOR_
LIMIT_2
64
Physical upper limit function of sensor2 (e.g. Pt 100 = +850°C) and
input range.
The unit of UPPER_SENSOR_LIMIT is the
PRIMARY_VALUE_UNIT.
Float
N
4
RO
850
LIN_TYPE_2
65
Select the type of sensor 2:
See LIN_TYPE for selection and supported types
Unsigned 8 SRC
1
R/W
102