Technical data
Parameter
Data
Pulse value
Last display digit unit/pulse, selection by
order code and setting can be read via
display menu, freely programmable by a
software tool
Pulse frequency
≤ 4 Hz
Pulse length
Typically 125 ms (100 … 150 ms)
External voltage supply
3 … 30 V DC
Current
≤ 20 mA
•
Energy (standard setting for 'Out1')
Possible pulse output selection
(max. output frequency: 4 Hz)
•
Volume (standard setting for 'Out2')
•
Tariff energy 1
•
Tariff energy 2
•
Tariff condition 1 (limit switch)
•
Tariff condition 2 (limit switch)
•
Energy error
•
Volume error
•
Volume in m
3
with specific display
resolution (or with factor 0,1, 10 or 100
thereof)
•
Energy with specific display resolution
(or factor 0.1 thereof)
•
Leakage detection (2 channel)
Pulse input
Type
Passive "open collector" pulse inputs,
outputs not potential isolated from each
other, data are separately cumulated in
different registers and are also stored on
the two accounting days.
Pulse value
Pulse value and the unit are configurable
for energy, water, gas or electrical meter
by a software tool
Pulse frequency
≤ 8 Hz
Pulse length
≥ 10 ms
External voltage supply
3 … 30 V DC
Current
Based on Ri = 2.2 M∧
Cable length
< 10 m connection limit
M-Bus output
Type
The optional M-Bus plug-in module is a
serial interface for communication with
external devices (M-Bus Repeater)
Protocol
M-Bus according to EN1434
Connection
Open collector,
2400/300 baud, 3.6 V
RS 232 output
Type
The optional plug-in RS232
communication module is a serial
interface and permits data exchange with
the calculator. For this purpose a special
data cable is necessary
Protocol
M-Bus according EN1434
SITRANS FUE950
Operating Instructions, 01/2010, SFIDK.PS.022.F4.02
59