
Connecting
5.5 Integrating the FC410 with Modbus system
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
49
Topology
FC410 supports a two-wire electrical interface in accordance with EIA/TIA-485 standard.
An RS485 Modbus configuration without repeater has one trunk cable, along which devices
are connected, directly (daisy chaining) or by short branch cables.
Note
Multidrop examples in this document show a trunk cable with short branch cables.
Maximum cable lengths
The end to end length of the trunk cable must be limited. The maximum length depends on
the baud rate, the cable (gauge, capacitance or characteristic Impedance), the number and
types of loads on the daisy chain, and the network configuration.
Note
Maximum branch cable length
Branch cables must be short, never more than 20 m.
Image 5-9
Maximum cable lengths in multidrop configuration