SFIDK.PS.029.Q3.02
41
7. Starting up
Starting up
SITRANS F US SONOFLO
®
®
®
®
®
Totalizer
Internal
Low flow cut-off can be set over a range from 0 - 9.9% of the measuring range.
In forced control it is possible to define the behavior of a current or frequency output in the event
of a fatal error. By selecting "off" the output remains on the latest valid reading.
MIN. forces the output to 0% in the event of an error and MAX. forces the outputs to 100%.
Select flow, direction and engineering units. By selecting bidirectional flow the net flow, i.e. the
difference between the positive and the negative flows, will be displayed.
Low flow cut-off
Forced control
Current output
CURRENT
OUT
CURRENT OUT
OFF
VOLUME FLOW
MASS FLOW
SOUND VELOCITY
CURRENT OUT
TIME CON.
XX.XS
CURRENT OUT
4 - 20 mA
0 - 20 mA
CURRENT OUT
BIDIRECTIONAL
UNIDIRECTIONAL
Current output
characteristics
Bidirectionel
Unidirectionel