
Digital output
Digital output can be used to configure various settings:
● Pulse (volume/pulse, pulse output, pulse width, pulse polarity, and time constant), see
● Frequency (frequency output, max frequency, and time constant), see Frequency menu
● Error settings (level and number), see Error level menu diagram (Page 79) and Error
number menu diagram (Page 80).
● Limit settings (number of setpoints, setpoint settings, and hysteresis), see Direction/limit
● Batch settings (quantity, time and counter settings, and time constant), see Batch menu
Note
When relay is set to batch function, pulse/frequency is not available on digital output.
Relay outputs
Relay output can be used to configure various settings:
● Error settings (level and number), see Error level menu diagram (Page 79) and Error
number menu diagram (Page 80).
● Limit settings (number of setpoints, setpoint settings, and hysteresis), see Direction/limit
● Batch settings (quantity, time and counter settings, and time constant), see Batch menu
See also
7.3
External input
By applying 11 … 30 V DC to terminals 77 and 78, it is possible to perform:
● Batch control (start, stop, hold/continue)
● Reset totalizer
● Force/freeze output
● Q
max
2 (night)
See external input menu diagram (Page 82).
Functions
7.3 External input
50
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018,
A5E02083319-AH