30
Utility Screens
Sensor Selection
1. Liquid applications can be serviced by any of 3 sensor types as follows;
∂
High Precision: The primary choice for steel pipes
∂
Universal:
For all non-steel and plastic pipes
∂
High Temperature: For all pipes with temperatures between 250 – 450F
2. The FS200 Liquid Tool will recommend the best suited sensor type and size based on
your programmed application data parameters. In many cases more than one type sensor
is acceptable. The FS200 tool will identify these sensors with the indication
“Recommended” or with an asterisk (*). Alternate types can be selected so long as you
choose recommended types and sizes, be aware if an “Application Problem” alert appears
3. The FS200 utility will also provide the recommended sensor part number and the
recommended mounting method
Figure 6-12 Liquid Sensor Type / Size Selection
Clamp-On Liquid Tool screen
The Clamp-On Liquid Tool screen presents data in 2 available views; [Application Calcs] and
[Repeatability Graph]. You may click on the appropriate tab for specific details related to the
specified application. The data shown under each tab is relative to the application parameters
you entered for pipe dimensions, liquid type, flow, and temperature in the liquid tool using the
units of measure you selected. Should an application conflict exist it will alert you with an
“Application Problem” message.
Application Calcs. Tab
Click on the [Application Calcs] tab for application specific information pertinent to the
installation of your flow sensors, including spacing recommendation and offset (LTN).
Additionally, fundamental data relative to transit-time values, signal phase shift, Reynolds
number, flow velocity range and repeatability are also presented in this view
Figure 6-13 Liquid Application Calculations
FS2
0
0 Programming Manual, 03/2020,
A5E02951525-AB