Functions
7.2 Overload protection function
SIRIUS 3RA6 Compact Starter
System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02
55
NOTICE
Risk of a new overload trip!
If a manual reset is performed within 3 minutes of the overload trip and the compact starter
switches on, there is a risk of a new overload trip occurring immediately due to the fact that
the motor/motor model may not yet have had a chance to cool down sufficiently (curve (4)).
Make sure that the motor has cooled down sufficiently before resetting the compact starter.
If there is no control voltage present following a manual or automatic reset, the motor model
will continue to cool down as per the motor (curve (1)).