Mounting And Commissioning
3.2 Checking Connection
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
83
One should check in the operational annunciations that the VT mcb trip was detected. A requirement for this is
that the auxiliary contact of the VT mcb is connected and correspondingly allocated.
Close the VT mcb again: The above annunciations appear under the "
going
" operational annunciations, i.e. with
the comment "
OFF
" (e.g. "
>L1 MCB Closed
" " "
OFF
").
If one of the indications does not appear, check the connection and allocation of these signals.
If the "
ON
" and "
OFF
" messages are exchanged, then the breaker auxiliary contact type should be checked and
corrected if necessary.