Mounting And Commissioning
3.1 Mounting And Connections
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
68
Input/output board C-I/O-1(7VU681)
Figure 3-5
Input/output board C-I/O-1 with representation of the jumper settings required for the board
configuration
In the version 7VU681, binary output BO 6 on the Input/Output module C-I/O-1 can be configured as normally
open or normally closed (see also overview diagrams in Appendix A.2).
Table 3-8
7VU681 Jumper position for the contact type of the relay for BO6
Jumper
Open in quiescent state
(NO)
Closed in quiescent state
(NC)
Presetting
X40
1-2
2-3
1-2