Appendix
A.3 Default Settings
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
106
A.3.2
Binary Input
A.3.2.1 7VU681 BI default configuration
A.3.3
Binary output
A.3.3.1 7VU681 BO default configuration
Binary Input
Function No.
Binary Input Allocated Function
BI1
17748
>BLOCK ATS
BI2
17759
>Manual.Restart
BI3
No functions configured
BI4
No functions configured
BI5
No functions configured
BI6
17622
>CB1 52b
CB1 Op/Cl
BI7
17621
>CB1 52a
CB1 Op/Cl
BI8
17624
>CB2 52b
CB2 Op/Cl
BI9
17623
>CB2 52a
CB2 Op/Cl
BI10
17626
>CB3 52b
CB3 Op/Cl
BI11
17625
>CB3 52a
CB3 Op/Cl
BI12
No functions configured
BI13
No functions configured
BI14
17864
>NonManu.Op.CB1
BI15
17865
>NonManu.Op.CB2
BI16
No functions configured
BI17
No functions configured
Binary Output
Function No.
Allocated Function
BO1
18013
ATS is Ready
BO2
18001
ATS Succeeded
BO3
18002
ATS Failed
Summary of Contents for SIPROTEC 7VU681
Page 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Page 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Page 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Page 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...