Table 3-12
Jumper setting of pickup voltages of binary inputs BI6
、
BI7 and BI16
、
BI17 on Input/Output
module C- I/O-11
1)
Factory settings for devices with rated power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115/230 VAC
3)
Use only with control voltages 220 to 250 VDC
The jumpers X71, X72 through X73 serve for setting the bus address. Their position may not be changed. The
following table shows the preset jumper positions.
Installation Place
Table 3-13
Jumper settings of module addresses of the input/output module C-I/O-11 (Left Slot 33 No.4)
Table 3-14
Jumper settings of module addresses of the input/output module C-I/O-11 (right Slot 33 No.3)
3.1.2.4
Interface Module
Replacing Interface Modules
The interface modules are located on the C-CPU-2 board. The following figure shows the PCB with location of
the modules.
Binary Input
Jumper
17 VDC Threshold
73 VDC Threshold
154 VDC Threshold
BI6
X21
L
M
H
BI7
X22
L
M
H
BI16
X21
L
M
H
BI17
X22
L
M
H
Jumper
Factory Setting
X71
1-2(H)
X72
2-3(L)
X73
1-2(H)
Jumper
Factory Setting
X71
1-2(H)
X72
1-2(H)
X73
2-3(L)
Summary of Contents for SIPROTEC 7VU681
Page 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Page 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Page 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Page 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...