Function
2.2 Protection
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
55
2.2.4.1
Settings
2.2.4.2
Information List
Addr.
Settings
Setting Options
Default Setting
Comments
Protection Functions -> General
9030
Earth O/C for Busbar
Energization
ON
OFF
OFF
9018
3I0/IE Assignment
IE
3I0
3I0
9019A
Active time for Busbar
Energization
0.01s..600.00s
5.00s
Protection Functions -> Voltage Control
9012
3U0 Overvoltage Threshold
1V..200V
30V
Protection Functions -> Ea. O/C Energiz
9031
3U0 Control
Yes
No
Yes
9033
Earth O/C-1 for Busbar Energ. 0.1A..35A
2A
9034
Earth O/C-1 Time Delay for
Busbar Energization
0s..60s,
∞
0.5s
9035
Earth O/C -2 for Busbar Ener-
gization
0.1A..35A
4A
9036
Earth O/C -2 Time Delay for
Busbar Energ.
0s..60s,
∞
0.1s
No.
Information
Type
Funcion No.
Inf. No.
17938
>>BLK Ea.O/C En.
SP
17945
Ea.O/C Ene.ACT.
OUT
17946
Ea.O/C Ene. OFF
OUT
17947
Ea.O/C Ene. BLK
OUT
17932
Ea.O/C-1Ener.PU
OUT
17933
Ea.O/C-1Ene.Tr.
OUT
200
58
17934
Ea.O/C-2Ener.PU
OUT
17935
Ea.O/C-2Ene.Tr.
OUT
200
60
17984
Ea.O/CEn.ON/OFF
IntSP
200
88
Summary of Contents for SIPROTEC 7VU681
Page 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Page 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Page 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Page 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...