Functions
2.2 Phase Comparison Protection and Ground Differential Protection
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
73
2.2.7.2
Differential Protection Commissioning
General
In differential protection commissioning mode (commissioning mode in the following) the differential protection
does not generate TRIP commands. The commissioning mode is intended to support the commissioning of the
differential protection.
You can check:
• transformer polarity, using the constellation measured values
• differential currents
• restraint currents
By editing parameters, the operating point of the differential protection can be changed without any risk up to
the generation of a pickup.
Figure 2-20
Commissioning mode - overview
The commissioning mode is activated on a device of the protective device constellation and also affects the
device at the other end of the protected object (indication no. 3193
„Comm. 87 active“
). The commissioning
mode has to be deactivated on the device on which it was activated.
The commissioning mode can be activated/deactivated as follows:
• Operation panel: Menu Control/Taggings/Set: „Commissioning mode“
• Via binary inputs (no. 3260
„>Comm. 87 ON“
, no. 3261
„>Comm. 87 OFF“
) if this was routed
• In DIGSI with Control / Taggings: „Diff: Commissioning mode“
Mode of Operation
Below, the logic is shown in a simplified way:
Figure 2-21
Logic diagram of the commissioning mode