2.14 Monitoring Functions
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
177
3-Phase Measuring Voltage Failure "Fuse Failure Monitor"
The minimum voltage below which a 3-phase measured voltage failure is detected is set in address
2913
FFM
V<max (3ph)
unless a current step takes place simultaneously which exceeds the limit according to address
2914
FFM Idiff (3ph)
. These settings can only be changed via DIGSI at
Display Additional Settings
.
In address
2910
FUSE FAIL MON.
, the „fuse failure monitor“ can be switched
OFF
e.g. during asymmetrical
testing.
Measured Voltage Failure Monitoring
In address
2915
V-Supervision
, the measured voltage failure monitoring can be switched to
w/
CURR.SUP
,
w/ I> & 52a
or
OFF
. Address
2916
T V-Supervision
is used to set the waiting time of the
voltage failure monitoring. This setting can only be changed using DIGSI at
Additional Settings
.
2.14.1.6 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2901
MEASURE. SUPERV
ON
OFF
ON
Measurement Supervision
2902A
BALANCE V-LIMIT
10 .. 100 V
50 V
Voltage Threshold for
Balance Monitoring
2903A
BAL. FACTOR V
0.58 .. 0.95
0.75
Balance Factor for Voltage
Monitor
2904A
BALANCE I LIMIT
1A
0.10 .. 1.00 A
0.50 A
Current Threshold for
Balance Monitoring
5A
0.50 .. 5.00 A
2.50 A
2905A
BAL. FACTOR I
0.10 .. 0.95
0.50
Balance Factor for Current
Monitor
2906A
Σ
I THRESHOLD
1A
0.10 .. 2.00 A
0.25 A
Summated Current Moni-
toring Threshold
5A
0.50 .. 10.00 A
1.25 A
2907A
Σ
I FACTOR
0.00 .. 0.95
0.50
Summated Current Moni-
toring Factor
2908A
T BAL. V LIMIT
5 .. 100 sec
5 sec
T Balance Factor for
Voltage Monitor
2909A
T BAL. I LIMIT
5 .. 100 sec
5 sec
T Current Balance Monitor
2910
FUSE FAIL MON.
ON
OFF
ON
Fuse Failure Monitor
2911A
FFM V>(min)
10 .. 100 V
30 V
Minimum Voltage Thresh-
old V>
2912A
FFM I< (max)
1A
0.10 .. 1.00 A
0.10 A
Maximum Current Thresh-
old I<
5A
0.50 .. 5.00 A
0.50 A
2913A
FFM V<max (3ph)
2 .. 100 V
5 V
Maximum Voltage Thresh-
old V< (3phase)