![Siemens SIPROTEC 7SD80 Manual Download Page 371](http://html.mh-extra.com/html/siemens/siprotec-7sd80/siprotec-7sd80_manual_382671371.webp)
Appendix
A.9 Information List
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
371
A.9
Information List
Indications for IEC 60 870-5-103 are always reported ON / OFF if they are subject to general interrogation for
IEC 60 870-5-103. If not, they are reported only as ON.
New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to ON / OFF and subjected
to general interrogation if the information type is not a spontaneous event („.._Ev“). Further information with
regard to the indications is set out in the SIPROTEC 4 System Description, Order No. E50417-H1100-C151.
In columns „Event Log“, „Trip Log“ and „Ground Fault Log“ the following applies:
UPPER CASE NOTATION “ON/OFF”:
definitely set, not allocatable
lower case notation “on/off”:
preset, allocatable
*: not
preset,
allocatable
<blank>:
neither preset nor allocatable
In the column „Marked in Oscill. Record“ the following applies:
UPPER CASE NOTATION “M”:
definitely set, not allocatable
lower case notation “m”:
preset, allocatable
*: not
preset,
allocatable
<blank>:
neither preset nor allocatable
No.
Description
Function
Type
of In-
for-
matio
n
Log Buffers
Configurable in Matrix
IEC 60870-5-103
Ev
ent L
og O
N
/O
FF
T
rip (Faul
t)
Log
ON/
O
F
F
Gr
ound
Fault L
og O
N
/O
FF
M
a
rk
ed
in
O
s
c
ill.
Re
c
o
rd
LED
Binar
y
Inpu
t
Function Key
Relay
Chatt
e
r Suppression
Ty
p
e
In
fo
rma
tio
n
Num
b
e
r
Da
ta
Unit
G
e
ne
ra
l I
n
te
rrog
a
tio
n
-
Test mode (Test mode)
Device, General
IntSP
On
Off
*
*
LED
BO
192
21
1
Yes
-
Stop data transmission (DataS-
top)
Device, General
IntSP
On
Off
*
*
LED
BO
192
20
1
Yes
-
Unlock data transmission via BI
(UnlockDT)
Device, General
IntSP
*
-
Reset LED (Reset LED)
Device, General
IntSP
ON
*
*
LED
BO
192
19
1
No
-
Clock Synchronization (Synch-
Clock)
Device, General
IntSP
_Ev
*
*
*
LED
BO
-
>Back Light on (>Light on)
Device, General
SP
On
Off
*
BI
-
Hardware Test Mode (HWTest-
Mod)
Device, General
IntSP
On
Off
*
*
LED
BO
-
Error FMS FO 1 (Error FMS1)
Device, General
OUT
On
Off
*
*
LED
BO
-
Error FMS FO 2 (Error FMS2)
Device, General
OUT
On
Off
*
*
LED
BO
-
Disturbance CFC (Distur.CFC)
Device, General
OUT
On
Off
*
LED
BO
-
Breaker OPENED (Brk
OPENED)
Device, General
IntSP
*
*
*
LED
BO
-
Feeder GROUNDED (Feeder
gnd)
Device, General
IntSP
*
*
*
LED
BO
-
Setting Group A is active (P-GrpA
act)
Change Group
IntSP
On
Off
*
*
LED
BO
192
23
1
Yes
-
Setting Group B is active (P-GrpB
act)
Change Group
IntSP
On
Off
*
*
LED
BO
192
24
1
Yes