![Siemens SIPROTEC 7SD80 Manual Download Page 280](http://html.mh-extra.com/html/siemens/siprotec-7sd80/siprotec-7sd80_manual_382671280.webp)
Mounting and Commissioning
3.4 Final Preparation of the Device
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
280
3.4
Final Preparation of the Device
Firmly tighten all screws. Tighten all terminal screws, including those that are not used.
Caution!
Inadmissible Tightening Torques
Non-observance of the following measure can result in minor personal injury or property damage:
The tightening torques must not be exceeded as the threads and terminal chambers may otherwise be dam-
aged!
The setting values should be checked again, if they were modified during the tests.
Check if protection,
control and auxiliary functions to be found with the configuration parameters are set correctly (Section 2.1.1,
Functional Scope). All desired elements and functions must be set
ON
. Ensure that a copy of the setting values
is stored on the PC.
The user should check the device-internal clock and set/synchronize it if necessary, provided that it is not syn-
chronized automatically. Refer to the SIPROTEC 4 System Description for more information on this.
The indication buffers are deleted under
Main Menu
→
Annunciation
→
Set/Reset
, so that in the future they
only contain information on actual events and states. The counters in the switching statistics should be reset to
the values that were existing prior to the testing (see also SIPROTEC 4 System Description).
The counters of the operational measured values (e.g. operation counter, if available) are reset under
Main
Menu
→
Measurement
→
Reset
(see also SIPROTEC 4 System Description).
Press the
ESC
key, several times if necessary, to return to the default display. The default display appears in
the display (e.g. display of operational measured values).
Clear the LEDs on the front panel by pressing the
LED
key, so that they only show real events and states. In
this context, saved output relays are reset, too. Pressing the
LED
key also serves as a test for the LEDs on the
front panel because they should all light when the button is pushed. If the LEDs display states relevant by that
moment, these LEDs, of course, stay lit.
The green „RUN“ LED must light up, whereas the red „ERROR“ must not light up.
Close the protective switches. If test switches are available, then these must be in the operating position.
The device is now ready for operation.
■