Mounting and Commissioning
3.2 Checking Connections
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
254
Connections at port B
Table 3-3
Assignments of the port B sockets
1)
Pin 7 also carries the RTS signal with RS232 level when operated as RS485 interface. Pin 7 must therefore
not be connected!
2)
For time synchronization via RS232, the X11 jumper must be in position 1-2.
Figure 3-19
Position of jumper X11 on the RS 232 interface
With data cables, the connections are designated according to DIN 66020 and ISO 2110:
• TxD = Data output
• RxD = Data input
• RTS = Request to send
• CTS = Clear to send
• GND = Signal/Chassis Ground
The cable shield is to be grounded at
both ends
. For extremely EMC-prone environments, the GND may be
connected via a separate individually shielded wire pair to improve immunity to interference.
Pin
No.
RS232
RS232
time syn-
chroniza-
RS485
Profibus DP,
RS485
Modbus RS485
DNP3.0 RS485
Ethernet
EN 100
IEC 60870–5–103
redundant
1
Shield (with shield ends electrically connected)
Tx+
B/B’ (RxD/TxD-P)
2
RxD
–
–
–
–
Tx–
A/A’ (RxD/TxD-N)
3
TxD
–
A/A’ (RxD/TxD-N)
B/B’ (RxD/TxD-P)
A
Rx+
–
4
–
–
–
CNTR-A (TTL)
RTS (TTL level)
—
–
5
GND
GND
C/C’ (GND)
C/C’ (GND)
GND1
—
–
6
–
–
–
+5 V (max. load <
100 mA)
VCC1
Rx–
–
7
RTS
–
–
–
—
–
8
CTS
CTS
B/B’ (RxD/TxD-P)
A/A’ (RxD/TxD-N)
B
—
–
9
–
–
–
–
–
not available
not available