Appendix
A.8 Settings
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
365
2634
51-B TD IEC
Back-Up O/C
0.05 .. 3.00 sec;
∞
0.50 sec
51-B Time Dial for IEC character-
istic
2634
67-TOC TD IEC
Back-Up O/C
0.05 .. 3.00 sec;
∞
0.50 sec
67-TOC Time Dial for IEC char-
acteristic
2635
51-B TD ANSI
Back-Up O/C
0.50 .. 15.00 ;
∞
5.00
51-B Time Dial for ANSI charac-
teristic
2635
67-TOC TD ANSI
Back-Up O/C
0.50 .. 15.00 ;
∞
5.00
67-TOC Time Dial for ANSI char-
acteristic
2636
51-B AddT-DELAY
Back-Up O/C
0.00 .. 30.00 sec
5.00 sec
51-B Additional Time Delay
2636
67-TOC AddTDel.
Back-Up O/C
0.00 .. 30.00 sec
5.00 sec
67-TOC Additional Time Delay
2637
51-B Inrush
Back-Up O/C
NO
YES
NO
51-B Inrush blocking
2637
67-TOC Inrush
Back-Up O/C
NO
YES
NO
67-TOC Inrush blocking
2638
51N-B PICKUP
Back-Up O/C
1A
0.05 .. 4.00 A;
∞
∞
A
51N-B Pickup
5A
0.25 .. 20.00 A;
∞
∞
A
2638
67N-TOC PICKUP
Back-Up O/C
0.05 .. 4.00 A;
∞
∞
A
67N-TOC Pickup threshold
2639
51N-B TD IEC
Back-Up O/C
0.05 .. 3.00 sec;
∞
0.50 sec
51N-B Time Dial for IEC charac-
teristic
2639
67N-TOC TD IEC
Back-Up O/C
0.05 .. 3.00 sec;
∞
0.50 sec
67N-TOC Time Dial for IEC char-
acteristic
2640
51N-B TD ANSI
Back-Up O/C
0.50 .. 15.00 ;
∞
5.00
51N-B Time Dial for ANSI char-
acteristic
2640
67N-TOC TD ANSI
Back-Up O/C
0.50 .. 15.00 ;
∞
5.00
67N-TOC Time Dial for ANSI
char.
2641
51N-B AddTdelay
Back-Up O/C
0.00 .. 30.00 sec
0.00 sec
51N-B Additional Time Delay
2641
67N-TOC AddTDel
Back-Up O/C
0.00 .. 30.00 sec
0.00 sec
67N-TOC Additional Time Delay
2642
IEC Curve
Back-Up O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
2642
IEC Curve
Back-Up O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
2643
ANSI Curve
Back-Up O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
2643
ANSI Curve
Back-Up O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
2644
51(N)-B PilotBI
Back-Up O/C
NO
YES
NO
Instantaneous trip via Pilot
Prot./BI
2644
67(N)TOC Pil/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via Pilot
Prot./BI
2650
50(N)-STUB OpMo
Back-Up O/C
ON
Only Emer. prot
OFF
OFF
50(N)-STUB Operating Mode
2651
50-STUB PICKUP
Back-Up O/C
1A
0.10 .. 25.00 A;
∞
1.50 A
50-STUB Pickup
5A
0.50 .. 125.00 A;
∞
7.50 A
2652
50-STUB DELAY
Back-Up O/C
0.00 .. 30.00 sec;
∞
0.30 sec
50-STUB Delay
2653
50-STUB Inrush
Back-Up O/C
NO
YES
NO
50-STUB Inrush blocking
2654
50N-STUB PICKUP
Back-Up O/C
1A
0.05 .. 25.00 A;
∞
0.20 A
50N-STUB Pickup
5A
0.25 .. 125.00 A;
∞
1.00 A
2655
50N-STUB DELAY
Back-Up O/C
0.00 .. 30.00 sec;
∞
2.00 sec
50N-STUB Delay
2656
50STUB Pilot/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via Pilot
Prot./BI
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments