[sctimedg-220415, 1, en_US]
Figure 3-33
Time Information in DIGSI
For every time source, you see the following:
•
Last received time (with date)
•
Receipt time of the last received time telegram
•
Configured type of timer
•
Indication of timer outage or failure
•
Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.
i
i
NOTE
All times displayed (also the time source) take into consideration the local time settings (zone and daylight
saving time of the device) in the form of a numerical offset for UTC (universal time).
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Time sync.
_:102
Time sync.:Time source
1
•
none
•
IRIG-B
•
DCF77
•
PI
•
SNTP
•
IEC 60870-5-103
•
PROFIBUS DP
•
Modbus
•
DNP3
•
IEEE 1588
•
IEC 60870-5-104
none
_:103
Time sync.:Time source
1 port
•
port J
•
port F
•
port E
•
port P
•
port N
•
port G
3.4.4
System Functions
3.4 Date and Time Synchronization
SIPROTEC 5, Fault Recorder, Manual
85
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...