Parameter: Flash-Memory Size
•
Recommended setting value
(_:10111:161) Flash-memory size
=
1000 MB
With the parameter
Flash-memory size
you specify a maximum memory capacity of the continuous
recorder on the mass storage.
If the flash memory becomes full while recording new fault records, the device automatically deletes the
oldest data in order to continue recording (ring buffer).
The record time is limited by the set flash memory size, number of routed tracks and by the averaging time.
i
i
NOTE
If you change the capacity of the recorder or delete a recorder instance, the flash memory of the device is
re-organized and all recordings of the device – not just those of the changed recorder – are automatically
and irrevocably deleted.
Before this, save your recordings by exporting them manually in DIGSI 5 or archiving them in SICAM PQS.
Then, delete your recordings in DIGSI 5 to avoid inconsistencies between new and old recordings.
i
i
NOTE
The setting aid
Estimated record time
is dimmed and thus, you cannot set or change it.
i
i
NOTE
Due to the internal administration data, the complete flash memory size for the storing of recordings is not
available. The
Estimated record time
provides user information that helps to estimate how many
recordings can be stored in the reserved flash memory. The actual size of a continuous record depends on
the degree of compression and the number of stored events.
Parameter: Averaging Time
•
Recommended setting value
(_:10111:112) Averaging time
=
600 s
With the parameter
Averaging time
, you determine the time range over which an average value is formed
and stored in the memory.
The average value is always formed over the entire averaging time.
i
i
NOTE
The angles are not determined but rather used at the end of the averaging time with the current value.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2731:1
General:Mode
•
off
•
on
on
Control
_:10111:161
Continuous 1:Flash-
memory size
0.200 GB to 14.800 GB
1.000 GB
_:10111:102
Continuous 1:Estimated
record time
0.0 day(s) to 214748364.7
day(s)
0.0 day(s)
7.2.8.5
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual
249
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...