Resetting the LED Group
Using the Reset the LED group function, you can reset the stored LEDs of the functions in one specific func-
tion group while the activated, stored LEDs of other functions in other function groups remain activated.
Operational Measured Values
The operational measured values are always present in the Voltage-current 3-phase function group and
cannot be removed.
The following table shows the operational measured values of the Voltage-current 3-phase function group:
Table 6-3
Operational Measured Values of the Voltage-Current 3-Phase Function Group
Measured Values
Primary Secon-
dary
% Referenced to
I
A
, I
B
, I
C
Phase currents
A
A
Rated operating current of the primary values
3I0
Calculated zero-sequence current A
A
Rated operating current of the primary values
I
N
Neutral-point phase current
A
A
Rated operating current of the primary values
I
NS
Sensitive ground current
A
mA
Rated operating current of the primary values
V
A
, V
B
, V
C
Phase-to-ground voltages
kV
V
Operating rated voltage of primary values/√3
V
AB
, V
BC
, V
CA
Phase-to-phase voltages
kV
V
Rated operating voltage of the primary values
V
0
Zero-sequence voltage
kV
V
Operating rated voltage of primary values/√3
V
NG
Neutral-point displacement
voltage
kV
V
Operating rated voltage of primary values/√3
f
Frequency
Hz
Hz
Rated frequency
P
total
Active power
(total power)
MW
W
Active power of the primary values
√3 · V
rated
· I
rated
Q
total
Reactive power
(total power)
Mvar
var
Reactive power of the primary values
√3 · V
rated
· I
rated
S
total
Apparent power
(total power)
MVA
VA
Apparent power of the primary values
√3 · V
rated
· I
rated
Cos φ
Active power factor
(abs)
(abs)
100 % corresponds to cos φ = 1
P
A
, P
B
, P
C
Phase-related active power
MW
W
Active power of the phase
V
rated phsx
· I
rated phsx
Q
A
, Q
B
, Q
C
Phase-related reactive power
Mvar
var
Reactive power of the phase
V
rated phsx
· I
rated phsx
S
A
, S
B
, S
C
Phase-related apparent power
MVA
VA
Apparent power of the phase
V
rated phsx
· I
rated phsx
The operational measured values are explained in more detail in chapter
9.3 Operational Measured Values
Application and Setting Notes
Parameter: Rated current
•
Default setting
(_:9451:101) Rated current
=
1000 A
The
Rated current
parameter is used to set the primary rated current. The
Rated current
specified
here is the reference value for the percentage-measured values and setting values made in percentages.
If the device works with the IEC 61850 protocol, then you change only the setting value of the parameter via
DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.
6.3.3
Function-Group Types
6.3 Function-Group Type Voltage/current 3-Phase
SIPROTEC 5, Fault Recorder, Manual
149
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...