The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter
Min. trigger
and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
•
Default setting
(_:19441:103) dM/dt rise active
=
no
•
Default setting
(_:19441:107) dM/dt rise (/Filter time)
=
0 var
•
Default setting
(_:19441:115) dM/dt rise hysteresis
=
0.980 p.u.
•
Default setting
(_:19441:112) Filter time
=
2 periods
With the
dM/dt rise active
parameter, you activate the gradient trigger in order to monitor the positive
gradients of the sum reactive power using the set filtering time (input in periods).
Parameter Value
Description
yes
The positive gradient of the sum reactive power is monitored.
no
The positive gradient of the sum reactive power is not monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt rise (/Filter
time)
and can be adjusted.
Parameter: dM/dt Drop Active - dM/dt Drop (/Filter Time) - dM/dt Drop Hysteresis - Filter Time
•
Default setting
(_:19441:104) dM/dt drop active
=
no
•
Default setting
(_:19441:108) dM/dt drop (/Filter time)
=
0 var
•
Default setting
(_:19441:116) dM/dt drop hysteresis
=
0.980 p.u.
•
Default setting
(_:19441:112) Filter time
=
2 periods
With the
dM/dt drop active
parameter, you activate the gradient trigger in order to monitor the negative
gradients of the sum reactive power using the set filtering time (input in periods).
Parameter Value
Description
yes
The negative gradient of the sum reactive power is monitored.
no
The negative gradient of the sum reactive power is not monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt drop (/Filter
time)
and can be adjusted.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Trigger P 1
_:19411:1
Trigger P 1:Mode
•
off
•
on
•
test
off
_:19411:111
Trigger P 1:Power direc-
tion
•
negative
•
positive
positive
_:19411:101
Trigger P 1:Max. trigger
active
•
no
•
yes
yes
_:19411:105
Trigger P 1:Max. trigger
1 A @ 100 Irated 0.20 W to 20000.00 W
120.00 W
5 A @ 100 Irated 0.60 W to 100000.00 W
600.00 W
_:19411:113
Trigger P 1:Max. trigger
hysteresis
0.900 p.u. to 0.990 p.u.
0.980 p.u.
_:19411:102
Trigger P 1:Min. trigger
active
•
no
•
yes
yes
7.4.4.6
Fault Recorder
7.4 Trigger Functions 1-Phase
294
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...